B-2
Option Module Parameters
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
Device Parameters
Parameter
No. Name and Description
Details
01 [Port Number]
Displays the drive port into which the Option
Module is installed. Typically, this will be Port
4, 5 or 6.
Default:
5
Minimum:
0
Maximum:
7
Type:
Read Only
02 [DLs From Net Cfg]
Sets the number of contiguous controller-to-
drive Datalinks (additional parameters) that
are included in the network I/O connection.
Logic Command and Reference are always
included in the I/O connection. This parameter
controls how many of the contiguous Host [DL
From Net xx] parameters (16 maximum) are
active. For example, if this parameter value is
set to “5,” then Host Parameters 01 - [DL
From Net 01] through 05 - [DL From Net 05]
will be updated.
Default:
0
Minimum:
0
Maximum:
16
Type:
Read/Write
Reset Required:
Yes
03 [DLs From Net Act]
Displays the value of Device Parameter 02 -
[DLs From Net Cfg] at the time the drive was
reset. This is the number of actual contiguous
controller-to-drive Datalinks that the drive is
expecting.
Default:
0
Minimum:
0
Maximum:
16
Type:
Read Only
04 [DLs To Net Cfg]
Sets the number of contiguous drive-to-
controller Datalinks (additional parameters)
that are included in the network I/O
connection. Logic Status and Feedback are
always included in the I/O connection. This
parameter controls how many of the
contiguous Host [DL To Net xx] parameters
(16 maximum) are active. For example, if this
parameter value is set to “5,” then Host
Parameters 17 - [DL To Net 01] through 21 -
[DL To Net 05] will be updated.
Default:
0
Minimum:
0
Maximum:
16
Type:
Read/Write
Reset Required:
Yes
05 [DLs To Net Act]
Displays the value of Device Parameter 04 -
[DLs To Net Cfg] at the time the drive was
reset. This is the number of actual contiguous
drive-to-controller Datalinks that the controller
is expecting.
Default:
0
Minimum:
0
Maximum:
16
Type:
Read Only
06 [Net Addr Src]
Displays the source from which the Option
Module node address is taken. This will be
either the Node Address switches (see
) or the value of Device
Parameter 07- [Net Addr Cfg].
Default:
0 = Switches
Values:
0 = Switches
1 = Parameters
Type:
Read Only
07 [Net Addr Cfg]
Sets the network node address for the Option
Module if Device Parameter 06 - [Net Addr
Src] is set to “1” (Parameters).
Default:
63
Minimum:
0
Maximum:
63
Type:
Read/Write
Reset Required: Yes
08 [Net Addr Act]
Displays the actual network node address
used by the Option Module.
Default:
63
Minimum:
0
Maximum:
63
Type:
Read Only