C-12
DeviceNet Objects
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
DPI Parameter Object
Class Code
To access “Host Config” parameters, use the Host DPI Parameter
Object (Class Code 0x9F).
Instances
The number of instances depends on the number of parameters in the
device. The total number of parameters can be read in Instance 0,
Attribute 0.
Class Attributes
Hexadecimal
Decimal
0x93
147
Instances (Hex.)
(Dec.)
Device
Example Description
0x0000 – 0x3FFF
0 – 16383
Host Drive
0
Class Attributes (Drive)
0x4000 – 0x43FF
16384 – 17407 Option Card
1
Drive Parameter 1 Attributes
0x4400 – 0x47FF
17408 – 18431 Port 1
2
Drive Parameter 2 Attributes
0x4800 – 0x4BFF 18432 – 19455 Port 2
…
…
0x4C00 – 0x4FFF 19456 – 20479 Port 3
16384
Class Attributes (Option Card)
0x5000 – 0x53FF
20480 – 21503 Port 4
16385
Option Card Parameter 1 Attributes
0x5400 – 0x57FF
21504 – 22527 Port 5
…
…
0x5800 – 0x5BFF 22528 – 23551 Port 6
0x5C00 – 0x5FFF 23552 – 24575 Port 7
0x6000 – 0x63FF
24576 – 25599 Port 8
0x6400 – 0x67FF
25600 – 26623 Port 9
0x6800 – 0x6BFF 26624 – 27647 Port 10
0x6C00 – 0x6FFF 27648 – 28671 Port 11
0x7000 – 0x73FF
28672 – 29695 Port 12
0x7400 – 0x77FF
29696 – 30719 Port 13
0x7800 – 0x7BFF 30720 – 31743 Port 14
Attribute ID Access Rule Name
Data Type
Description
0
Get
Number of Instances
UINT
Number of parameters in the device
1
Set
Write Protect Password
UINT
0 = Password disabled
n = Password value
2
Set
NVS Command Write
USINT
0 = No Operation
1 = Store values in active memory to NVS
2 = Load values in NVS to active memory
3 = Load default values to active memory
4 = Partial defaults
5 = System defaults
3
Get
NVS Parameter Value Checksum
UINT
Checksum of all parameter values in a user set in NVS
4
Get
NVS Link Value Checksum
UINT
Checksum of parameter links in a user set in NVS
5
Get
First Accessible Parameter
UINT
First parameter available if parameters are protected by
passwords. A “0” indicates all parameters are protected.
7
Get
Class Revision
UINT
2 = DPI
8
Get
First Parameter Processing Error
UINT
The first parameter that has been written with a value
outside of its range. A “0” indicates no errors.
9
Set
Link Command
USINT
0 = No Operation
1 = Clear All Parameter Links (This does not clear links
to function blocks.)