A-4
Supplemental Information
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
Feedback
Encoder Inputs (2):
Dual Channel Plus Marker, Isolated with differential transmitter
Output (Line Drive) Incremental, Dual Channel Quadrature type
Dual Channel Plus Marker, Isolated with differential transmitter
Output (Line Drive) Incremental, Dual Channel Quadrature type
Encoder PPR Rating:
Encoder PPR ratings are limited to the values specified in the table below:
Encoder Voltage
Supply:
5V DC or 12 V DC 320 mA/channel
5V DC minimum high state voltage of 3.0V DC, maximum low
state voltage at 0.4V DC
12 V DC minimum high state voltage of 7.0V DC, maximum low
state voltage of 0.4V DC
5V DC or 12 V DC 320 mA/channel
5V DC minimum high state voltage of 3.0V DC, maximum low
state voltage at 0.4V DC
12 V DC minimum high state voltage of 7.0V DC, maximum low
state voltage of 0.4V DC
Maximum Input
Frequency:
400 kHz
400 kHz
Stegmann Option:
Encoder Voltage
Supply:
11.5V DC @ 130 mA
11.5V DC @ 130 mA
Hi-Resolution
Feedback:
Sine/Cosine 1V P-P Offset 2.5
Sine/Cosine 1V P-P Offset 2.5
Maximum Cable
Length:
182 m (600 ft.)
182 m (600 ft.)
RS-485 Interface:
Hi-Resolution Feedback Option card obtains the following
information via the Hiperface RS-485 interface shortly after
power-up: Address, Command Number, Mode, Number of turns,
Number of Sine/Cos cycles, Checksum
Hi-Resolution Feedback Option card obtains the following
information via the Hiperface RS-485 interface shortly after
power-up: Address, Command Number, Mode, Number of turns,
Number of Sine/Cos cycles, Checksum
Customer-I/O Plug (P1)
- Hi Res:
Allen-Bradley PN: S94262912
Weidmuller PN: BL3.50/90/12BK
Allen-Bradley PN: S94262912
Weidmuller PN: BL3.50/90/12BK
Resolver Option:
Excitation Frequency:
2400 Hz
2400 Hz
Excitation Voltage:
4.25-26 Vrms
4.25-26 Vrms
Operating Frequency
Range:
1 - 10 kHz
1 - 10 kHz
Resolver Feedback
Voltage:
2V ± 300 mV
2V ± 300 mV
Maximum Cable
Length:
304.8 meters (1000 ft.)
304.8 meters (1000 ft.)
DriveLogix
User Available
MemoryBase:
1.5 megabytes
1.5 megabytes
Battery:
1769-BA 0.59g lithium
1769-BA 0.59g lithium
Serial Cable:
1761-CBLPM02 to 1761-NET-AIC
1761-CBLPM02 to 1761-NET-AIC
1761-CBLPA00 to 1761-NET-AIC
1761-CBLPA00 to 1761-NET-AIC
1756-CP3 directly to controller
1756-CP3 directly to controller
1747-CP3 directly to controller
1747-CP3 directly to controller
category 3 (2)
category 3 (2)
Compact I/O Connection: Up to (16) modules
Up to (16) modules
Cable:
20D-DL2-CL3
20D-DL2-CR3
20D-DL2-CL3
20D-DL2-CR3
Category
Specification
Frames 1-6 (690V Drive frames 5 & 6 only)
Frames 9 & up
PPR Rating Values:
n = 2
n
=
x mod 75
mod 125
mod 225
mod 375
mod 625
mod1125
0
1
75
125
225
375
625
1125
1
2
150
250
450
750
1250
2250
2
4
300
500
900
1500
2500
4500
3
8
600
1000
1800
3000
5000
9000
4
16
1200
2000
3600
6000
10000
18000
5
32
2400
4000
7200
12000
20000
--
6
64
--
--
--
--
--
--
7
128
--
--
--
--
--
--
8
256
--
--
--
--
--
--
9
512
--
--
--
--
--
--
10
1024
--
--
--
--
--
--
11
2048
--
--
--
--
--
--
12
4096
--
--
--
--
--
--
13
8192
--
--
--
--
--
--
14
16384
--
--
--
--
--
--
Содержание PowerFlex 700S
Страница 1: ...USER MANUAL Firmware Versions 1 xxx 4 002 PowerFlex 700S High Performance AC Drive Phase II Control ...
Страница 58: ...2 8 Start Up PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 147: ...Programming and Parameters 3 89 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 278: ...D 8 HIM Overview PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 316: ...Index 6 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 317: ......