Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
77
Appendix
A
Specifications
440R-ENETR Specifications
Attribute
440R-ENETR
Indicators
Two red/green status indicators:
• Module status
• Network status (Ports 1 and 2 combined)
Two green/yellow status indicators:
• Link 1 status
• Link 2 status
Power consumption, max
2.2 W @ 26.4V DC
Power dissipation, max
0.8 W @ 26.4V DC
Thermal dissipation, max
2.7 BTU/hr @ 26.4V DC
Dimensions (HxWxD), approx.
111.4 x 22.5 x 113.6 mm (4.39 x 0.89 x 4.47 in.)
Enclosure type rating
None (open-style)
Terminal screw torque
0.4 N•m (4 lb•in)
Weight, approx.
180 g (0.4 lb)
Wiring category
– on power ports
– on communications ports
Wire size
Power connections:
0.34…2.1 mm2 (22…14 AWG) solid or
stranded copper wire, rated @ 75 °C (167 °F)
or greater, 1.2 mm (3/64 in.) insulation max
Ethernet wiring:
RJ45 connector according to IEC 60603-7, 2
or 4 pair Category 5e min cable according
to TIA 568-B.1 or Category 5 cable
according to ISO/IEC 24702.
North American temp code
T6
IEC temp code
T6
Temperature, operating
IEC 60068-2-1 (Test Ad, operating cold), IEC 60068-2-2 (Test Bd, operating dry heat),
IEC 60068-2-14 (Test Nb, operating thermal shock): -20…+55 °C (-4…+131 °F)
Temperature, surrounding air, max
55 °C (131 °F)
Temperature, nonoperating
IEC60068-2-1 (Test Ab, unpackaged nonoperating cold) IEC60068-2-2 (Test Bb, unpackaged
nonoperating dry heat), IEC60068-2-14 (Test Na, unpackaged nonoperating thermal shock):
-40…+85 °C (-40…+185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, unpackaged damp heat): 5...95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, operating): 5 g @ 10...500 Hz
Shock, operating
IEC60068-2-27 (Test Ea, unpackaged shock): 15 g
Emissions
CISPR 11: Group 1, Class A
ESD immunity
IEC61000-4-2: 6 kV contact discharges 8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
• 10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz 10V/m with 200 Hz 50% Pulse
100% AM @ 900 MHz
• 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 10V/m with 1 kHz sine-wave 80% AM
from 2000...2700 MHz
EFT/B immunity
IEC 61000-4-4:
• ±4 kV @ 5 kHz on power ports
• ±2 kV @ 5 kHz on communications ports
Surge transient immunity
IEC 61000-4-5:
• ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
• ±2 kV line-earth (CM) on communications ports
Conducted RF immunity
IEC61000-4-6:
• 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Содержание Guardmaster 440R-ENETR
Страница 12: ...12 Rockwell Automation Publication 440R UM009C EN P July 2019 Chapter 1 Product Overview Notes...
Страница 62: ...62 Rockwell Automation Publication 440R UM009C EN P July 2019 Chapter 6 AOP ControllerTags Notes...
Страница 76: ...76 Rockwell Automation Publication 440R UM009C EN P July 2019 Chapter 9 Explicit Communication Notes...
Страница 78: ...78 Rockwell Automation Publication 440R UM009C EN P July 2019 Appendix A Specifications Notes...
Страница 80: ...80 Rockwell Automation Publication 440R UM009C EN P July 2019 Appendix B Regulatory Approvals Notes...
Страница 84: ...84 Rockwell Automation Publication 440R UM009C EN P July 2019 Index Notes...
Страница 85: ......