Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
53
AOP Controller Tags
Chapter 6
EM and EMD Fault Codes
Table 12 - EM and EMD Relay Nonrecoverable Fault Codes
Fault Code
Decimal (Hex)
Description
Recommended Action
00 (00)
No fault
No action necessary.
01 (01)
RAM test
Follow the general instructions for faults. See
General Instructions for Faults on page 39
02 (02)
Stack over-/under-flow
03 (03)
Configuration mismatch between
Processors A and B
04 (04)
Internal timing
05 (05)
EEPROM read/write failure
06 (06)
B1 configuration
Check the wiring to terminal B1.
07 (07)
Mismatch between current switch
settings (switch 1: Range) and setting
stored during power-up.
Change the switch settings to the correct values.
08 (08)
Mismatch between current switch
settings (switch 2: Time) and setting
stored during power-up.
09 (09)
SPI compare fault
Follow the general instructions for faults. See
General Instructions for Faults on page 39
11 (0B)
ROM test failure
17 (11)
Pulse test fault on main transistor
18 (12)
Pulse test fault of transistor for safety
output channel 1
19 (13)
Pulse test fault of transistor for safety
output channel 2
20 (14)…24 (18)
Internal plausibility test fault
25 (19)
Relay contact K1
26 (1A)
Relay contact K2
27 (1B)
Relay contact K3
28 (1C)
Relay contact K4
29 (1D), 30 (1E)
Internal plausibility test.
31 (1F)
Different Single Wire Safety input
signal is detected at Processor A than
Processor B
32 (20), 33 (21)
Internal program
34 (22), 35 (23)
Rotary switch read error
36 (24)
Cross fault at processor pins for safety
outputs.
37 (25)
Under voltage detected
Measure and adjust the voltage at terminal A1 to 20.4…26.4V under all electrical load conditions.
38 (26)
Fault detected in the other Processor
Follow the general instructions for faults. See
General Instructions for Faults on page 39
42 (30)
Capacitor short detected
Содержание Guardmaster 440R-ENETR
Страница 12: ...12 Rockwell Automation Publication 440R UM009C EN P July 2019 Chapter 1 Product Overview Notes...
Страница 62: ...62 Rockwell Automation Publication 440R UM009C EN P July 2019 Chapter 6 AOP ControllerTags Notes...
Страница 76: ...76 Rockwell Automation Publication 440R UM009C EN P July 2019 Chapter 9 Explicit Communication Notes...
Страница 78: ...78 Rockwell Automation Publication 440R UM009C EN P July 2019 Appendix A Specifications Notes...
Страница 80: ...80 Rockwell Automation Publication 440R UM009C EN P July 2019 Appendix B Regulatory Approvals Notes...
Страница 84: ...84 Rockwell Automation Publication 440R UM009C EN P July 2019 Index Notes...
Страница 85: ......