Parameter Descriptions
3-37
The Accel Time parameters set the rate at which the drive ramps to its output
frequency after a start command or during an increase in command frequency (speed
change). The rate established is the result of the following equation:
(Maximum Speed / Accel Time) = Accel Rate
Two accel times exist to enable acceleration rate changes “on the fly” using a building
automation system command or digital input, if configured.
Sets the rate of deceleration for all speed decreases.
(Max Speed / Decel Time) = Decel Rate
Two decel times exist to enable deceleration rate changes “on the fly” using a building
automation system command or digital input, if configured.
Enables/disables dynamic brake operation when drive is stopped. DB may operate
when drive is stopped. DB may operate if input voltage becomes too high.
Disabled =
DB will only operate when drive is running.
Enabled =
DB will only operate when the drive is energized.
140
141
Accel Time 1
Accel Time 2
Range:
0.0 to 3600.0 [0.1 sec]
Default:
10.0 secs
Access:
140=0
141=2
Path:
Dynamic Control>Ramp Rates
See also:
142, 143, 146, 361
142
143
Decel Time 1
Decel Time 2
Range:
0.0 to 3600.0 sec [0.1 sec]
Default:
10.0 secs
Access:
142=0
143=2
Path:
Dynamic Control>Ramp Rates
See also:
140, 141, 146, 361
145
DB While Stopped
Range:
0 = Disabled
1 = Enabled
Default:
0 = Disabled
Access:
2
Path:
Dynamic Control>Stop/Brake Modes
See also:
161, 162