
Parameter Descriptions
3-15
Provides an automatic method of setting Total Inertia. This test is automatically run
during Start-Up motor tests.
Important:
Use when motor is coupled to the load. Results may not be valid if the
load is not coupled to the motor during this procedure.
Ready =
Parameter returns to this setting following a completed inertia tune.
Inertia Tune =
A temporary command that initiates an inertia test of the motor/load
combination. The motor will ramp up and down, while the drive measures the amount
of inertia.
Sets the voltage boost level for starting and acceleration when Custom V/Hz mode is
selected.
Sets the boost level for steady state or deceleration when Fan/Pmp V/Hz or Custom
V/Hz modes are selected.
Sets the voltage the drive will output at Break Frequency (72).
67
Inertia Autotune
Range:
0 = Ready
1 = Inertia Tune
Default:
0 = Ready
Access:
1
Path:
Motor Control>Torq Attributes
See also:
53, 450
FV
69
Start/Acc Boost
Range:
0.0 to Motor NP Volts x 0.25 [0.1 VAC]
Default:
Based on drive rating
Access:
2
Path:
Motor Control>Volts per Hertz
See also:
53, 70
70
Run Boost
Range:
0.0 to Motor NP Volts x 0.25 [0.1 VAC]
Default:
Based on drive rating
Access:
2
Path:
Motor Control>Volts per Hertz
See also:
53, 69,
71
Break Voltage
Range:
0.0 to Motor NP Volts [0.1 VAC]
Default:
Motor NP Volts x 0.25
Access:
2
Path:
Motor Control>Volts per Hertz
See also:
53, 72
Содержание CNMD180W0ENNNC1
Страница 1: ...Instruction Manual Reach Drive User Manual Manufactured for DBT D2 3561 ...
Страница 206: ...B 4 DBT Reach Drive Manual ...
Страница 238: ...Appendix D 24 DBT Reach Drive User Manual ...
Страница 247: ......