Installation/Wiring
2-7
2.5
I/O Wiring
Important points to remember about I/O wiring:
•
Use Copper wire only. Wire gauge requirements and recommendations are based
on 75 degrees C. Do not reduce wire gauge when using higher temperature wire.
•
Wire with an insulation rating of 600V or greater is recommended.
•
Control and signal wires should be separated from power wires by at least 0.3
meters (1 foot).
Important:
I/O terminals labeled “(–)” or “Common” are not referenced to earth
ground and are designed to greatly reduce common mode interference.
Grounding these terminals can cause signal noise.
Figure 2.5 – Power Termination Locations (U, V, W, R, S, T)
T
S
R
!
ATTENTION:
Configuring an analog input for 0-20mA operation and
driving it from a voltage source could cause component damage. Verify
proper configuration prior to applying input signals.
ATTENTION:
Hazard of personal injury or equipment damage exists
when using bipolar input sources. Noise and drift in sensitive input circuits
can cause unpredictable changes in motor speed and direction. Use
speed command parameters to help reduce input source sensitivity.
Содержание CNMD180W0ENNNC1
Страница 1: ...Instruction Manual Reach Drive User Manual Manufactured for DBT D2 3561 ...
Страница 206: ...B 4 DBT Reach Drive Manual ...
Страница 238: ...Appendix D 24 DBT Reach Drive User Manual ...
Страница 247: ......