ArmorStart
®
EtherNet/IP
™
Communications & Control Programming Manual
Chapter
4
4.
Reset the unit back to the factory default values by clicking on the
Reset
Defaults
button.
5.
The following screen will pop up. This screen is confirming that you want
to reset the parameters within the ArmorStart unit. Click
Yes
to continue.
6.
This screen will pop up letting you know that the parameters have been
reset to their default values. Click
OK
to continue.
7.
Scroll through the parameter list to parameters 24, 30, 31, 106, and 107.
a. Parameter 24 allows the user to enable or disable various protection
faults. Click on the value for parameter 24 and, using the scroll bar,
scroll down and check the box next to
A3 Power Loss
to enable this
fault. Choosing this causes the unit to fault if the unswitched A3
terminal power drops below 12V DC. The unswitched A3 terminal
powers both the inputs and the communications.