Programming and Parameters
Chapter 4
Inputs and Outputs File
Fil
e
Gr
oup
No.
Parameter Name and Description
Values
INPU
TS and OUTPUTS
An
al
og
In
pu
ts
200
[Anlg In Config]
Selects the mode for the analog inputs.
201
[Analog In 1 Hi]
Sets the highest input value to the Analog Input 1 scaling block.
Parameter 200 [Anlg In Config] defines if this input is -/+10V or 4…20 mA.
Default:
Min/Max:
Units:
10.000V
4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V
202
[Analog In 1 Lo]
Sets the lowest input value to the Analog Input 1 scaling block.
Parameter 200 [Anlg In Config] defines if this input is -/+10V or 4…20 mA.
Default:
Min/Max:
Units:
0.000V
4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V
203
[Analog In 1 Loss]
Selects the AFE action when an analog signal loss is detected. Signal loss is defined as an analog signal
less than 1V or 2 mA. The signal loss event ends and normal operation resumes when the input signal
level is greater than or equal to 1.5V or 3 mA.
Default:
Options:
0
0
1
2
3
4
Disabled
Disabled
Fault
Hold Input
Set Input Lo
Set Input Hi
204
[Analog In 2 Hi]
Sets the highest input value to the Analog Input 2 scaling block.
Parameter 200 [Anlg In Config] defines if this input is -/+10V or 4…20 mA.
Default:
Min/Max:
Units:
10.000V
4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V
205
[Analog In 2 Lo]
Sets the lowest input value to the Analog Input 2 scaling block.
Parameter 200 [Anlg In Config] defines if this input is -/+10V or 4…20 mA.
Default:
Min/Max:
Units:
0.000V
4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V
206
[Analog In 2 Loss]
Selects the AFE action when an analog signal loss is detected. Signal loss is defined as an analog signal
less than 1V or 2 mA. The signal loss event ends and normal operation resumes when the input signal
level is greater than or equal to 1.5V or 3 mA.
Default:
Options:
0
0
1
2
3
4
Disabled
Disabled
Fault
Hold Input
Set Input Lo
Set Input Hi
Anal
og
O
utput
s
207
[Anlg Out Config]
Selects the mode for the analog outputs.
Important:
Make sure that the jumpers are in the correct position or the output is wrong:
J3 = Analog Output 1; J4 = Analog Output 2
Position AB = Current; Position BC = Voltage 0-10V (default); Position CD = Voltage -/+10V
Bit
Definition
An2 (0 = V
, 1
= m
A)
An1 (0 = V
, 1
= m
A)
Default
x
x
x
x
x
x
x
x
x
x
x
x
x
x
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
1 = Current
0 = Voltage
x = Reserved
Bit
Definition
An2 (0 = V
, 1 = m
A)
An1 (0 = V
, 1 = m
A)
Default
x
x
x
x
x
x
x
x
x
x
x
x
x
x
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
1 = Current
0 = Voltage
x = Reserved
Содержание Allen-Bradley PowerFlex 700AFE
Страница 8: ...8 Rockwell Automation Publication 20Y UM001F EN P April 2017 Table of Contents Notes ...
Страница 124: ...124 Rockwell Automation Publication 20Y UM001F EN P April 2017 Chapter 4 Programming and Parameters Notes ...
Страница 136: ...136 Rockwell Automation Publication 20Y UM001F EN P April 2017 Chapter 5 Troubleshooting Notes ...
Страница 158: ...158 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix A Supplemental Information Notes ...
Страница 164: ...164 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix B HIM Overview Notes ...
Страница 180: ...180 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index by number 120 linear list 120 viewing 163 ...
Страница 184: ...184 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index Notes ...
Страница 185: ......