Rockwell Automation Publication 6000-UM002G-EN-P - August 2022
99
Chapter 5 Preventative Maintenance and Component Replacement
Figure 42 - Power Module Component Location, A-Frame
Figure 43 - Power Module Component Location, H-Frame and B-Frame
3. Remove the output copper bars that connect adjacent Power Modules
(
If the Power Module is at the end of a row, remove the VSB and motor
cable instead of an output copper bus.
4. Disconnect the fiber-optic cables.
Fuse
Output copper bar
connection location
Fiber-optic cables connection point
Three-phase input cables
from isolation transformer
M6 x 16 hexagon
combination screws (2)
Fuse
Output copper bar (not shown)
connection location
Fiber-optic cables connection point
Three-phase input cables
from isolation transformer
M6 x 20 mounting bolt
ATTENTION:
When removing the fiber-optic cables, be careful to prevent the
cables from straining or crimping as the resulting loss in light transmission
will impact performance.