Rockwell Automation Publication 6000-UM002G-EN-P - August 2022
123
Chapter 5 Preventative Maintenance and Component Replacement
Inspect Power Module Input and Output Power Connections
Verify that all Power Module input line cables and output bus connections are
properly torqued. Verify that the output cables, VSB Cables, and star
connection cables are properly torqued. Apply torque sealer if necessary. Check
for corrosion, excessive temperature, or contamination.
General
Review Firmware and Hardware
Verify the firmware revision on the HMI. Contact Rockwell Automation to
determine whether there are any enhancements or changes that are made to
the Drive Hardware and Control that would be valuable to the application.
Verify that the HMI is operational. Check the status indicators on the Control
Unit in the LV Control cabinet register as normal.
Remove any dirt or foreign material. Wipe components with an anti-static
cloth, where applicable.
Inspect/Review Spare Parts
Inspect and review the spare parts that are shipped with the drive (see the
packing list if applicable). Check for signs of damage, dirt, or foreign material.
Professional Maintenance Service
Rockwell Automation also offers professional maintenance service that is
provided by the Rockwell Automation field support engineer, contact your
local Rockwell Automation sales person for more information.
Miscellaneous Preventive Maintenance Work
•
Communicate with the customer regarding problems found during the
preventive maintenance process.
•
Raise the problems found during the maintenance process.
•
Provide relevant solutions and record them in the final report.
•
Provide advice on operation and maintenance of the drive to the
customer’s maintenance personnel.
•
Provide information about requirements for safe operation of the drive
and safety instructions.
•
Provide information about operating conditions (environment,
temperature, and so on) required for stable operation of the drive.
ATTENTION:
Verify that there is no power to the drive and wear an anti-static
wristband.
ATTENTION:
Some circuit boards can be destroyed by static charges. Use of
damaged circuit boards may also damage related components. Use a
grounding wriststrap when handling sensitive circuit boards.
ATTENTION:
Due to the characteristics of DC capacitors, rejuvenation is
necessary on power module DC capacitors if the power module has not been
energized in the last one year. Therefore the spare power modules need to be
energized annually.
Содержание Allen-Bradley PowerFlex 6000
Страница 10: ...10 Rockwell Automation Publication 6000 UM002G EN P August 2022 Preface Notes ...
Страница 82: ...82 Rockwell Automation Publication 6000 UM002G EN P August 2022 Chapter 4 Parameters and Function Codes Notes ...
Страница 134: ...134 Rockwell Automation Publication 6000 UM002G EN P August 2022 Appendix C Preventative Maintenance Schedule Notes ...
Страница 136: ...136 Rockwell Automation Publication 6000 UM002G EN P August 2022 Appendix D Torque Requirements Notes ...
Страница 148: ...148 Rockwell Automation Publication 6000 UM002G EN P August 2022 Appendix E Spare Parts Storage Notes ...