Rockwell Automation Publication 6000-UM002G-EN-P - August 2022
Chapter 5 Preventative Maintenance and Component Replacement
Replace LV Control Circuit Breakers
1. Open the LV Control cabinet door.
2. Switch the circuit breaker to the off position.
Figure 68 - Circuit Breaker Location in LV Control Cabinet
3. Loosen the top and bottom screws and remove the wires on the circuit
breaker.
Figure 69 - Screw location on Circuit Breaker
4. Release the spring-loaded latches at the bottom of the circuit breaker and
lift the circuit breaker off the DIN rail.
ATTENTION:
Always perform Power Lockout procedure before servicing
equipment. Verify with a hot stick or appropriate voltage measuring device
that all circuits are voltage free. Failure to do so may result in severe burns,
injury, or death.
Circuit breaker switch must
be in the Off position
Loosen screws and
remove wires
Loosen screws and
remove wires