Component Test Procedures
Save the Parameter
Configuration
It is recommended that you save the drive and communication adapter parameter
configuration to a HIM set or by up loading the drive and adapter parameters to
an offline node file using Connected Components Workbench™ or
DriveExecutive™ software before performing any service or testing on the drive.
HIM sets are files stored in permanent nonvolatile HIM memory.
Save to a HIM Set
Follow these steps to save the drive and communication adapter parameters to a
HIM set.
1.
On the HIM, access the
Memory Storage
menu.
2.
Select the
HIM CopyCat
menu and press
.
3.
Select
Device
->
HIM
and press
.
4.
Do one of the following:
•
If there are no existing HIM sets, enter a name using the
and
buttons to select the desired characters and press
.
•
If there is an existing HIM set, press
to overwrite it, or select
No
using the
button and use the
and
buttons to select
the desired characters. Then press
.
The HIM set will be saved to nonvolatile memory.
Содержание Allen-Bradley PowerFlex 20P
Страница 1: ...PowerFlex Digital DC Drive Frame D Bulletin Number 20P Hardware Service Manual Original Instructions ...
Страница 8: ...8 Rockwell Automation Publication 20P TG004C EN P September 2021 Preface Notes ...
Страница 42: ...42 Rockwell Automation Publication 20P TG004C EN P September 2021 Chapter 2 ComponentTest Procedures Notes ...
Страница 108: ...108 Rockwell Automation Publication 20P TG004C EN P September 2021 Chapter 3 Access Procedures Notes ...
Страница 136: ...136 Rockwell Automation Publication 20P TG004C EN P September 2021 Appendix D History of Changes Notes ...
Страница 140: ...140 Rockwell Automation Publication 20P TG004C EN P September 2021 Index Notes ...