background image

12

Rockwell Automation Publication 1734-IN032F-EN-P - September 2022

POINT I/O 4 Channel High Density Current Input Module Installation Instructions

Normal mode rejection ratio

-60 dB

Notch Filter

13.1 Hz @ Notch = 50 Hz

15.7 Hz @ Notch = 60 Hz (default)

26.2 Hz @ Notch = 100 Hz

31.4 Hz @ Notch = 120 Hz

52.4 Hz @ Notch = 200 Hz

62.9 Hz @ Notch = 240 Hz

78.6 Hz @ Notch = 300 Hz

104.8 Hz @ Notch = 400 Hz

125.7 Hz @ Notch = 480 Hz

Data format

Signed integer

Maximum overload

Fault protected to 28.8V DC

Calibration

Factory calibrated

Indicators, logic side

1 green/red network status

1 green/red module status

4 green/red input status

(1) Includes offset, gain, non-linearity, and repeatability error terms.

IMPORTANT

See the POINT I/O Modules Selection Guide, publicatio

1734-SG001

 for information on breaking the field power distribution bus. See sections 

“When to Use the Field Power Distributor” and “When to Use the Expansion Power Unit”.

General Specifications

Attribute

Value

Terminal base

1734-TB3, 1734-TB3S wiring base assembly

POINTBus™ current, max

75 mA

Power dissipation, max

0.55 W @ 28.8V DC

Thermal dissipation, max

2.0 BTU/hr @ 28.8V DC

Supply voltage, backplane

5V DC

Supply voltage range, field power input

10…28.8V DC, 20 mA, Class 2

Input current

4…20 mA or 0…20 mA

Isolation voltage

50V, tested @ 1500V AC for 60 s, inputs, and field power to system

No isolation between individual inputs or inputs to field power

Dimensions (H x W x D), approx.

56.0 x 12.0 x 75.5 mm

(2.21 x 0.47 x 2.97 in.)

Keyswitch position

3

Enclosure type rating

None (open-style)

Wire size

0.25…2.5 mm

2

 (22…14 AWG) solid or stranded copper wire rated at 100 °C (212 °F), or greater, 

1.2 mm (3/64 in.) insulation max

Wiring category

(1)

(1) Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring and Grounding Guidelines, publication 

1770-4.1

.

2 – on signal ports

1 – on power ports

Wire type

Shielded

Terminal base screw torque

Determined by installed terminal block

Weight, approx.

35 g (1.235 oz)

North American temp code

T4A

UKEX/ATEX temp code

T4

IECEx temp code

T4

Input Specifications (Continued)

Attribute

Value

Содержание Allen-Bradley POINT I/O 1734-IE4C

Страница 1: ...ubstantive updates only and is not intended to reflect all changes Topic Page Summary of Changes 1 Before You Begin 5 Install the Mounting Base 6 Install the Module 7 Install the Removable Terminal Bl...

Страница 2: ...ocumento ed i documenti elencati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell apparecchiatura Gli utenti devono leggere e comprendere le istruzion...

Страница 3: ...are suitable for use in Class I Division 2 Groups A B C D Hazardous Locations and nonhazardous locations only Each product is supplied with markings on the rating nameplate indicating the hazardous l...

Страница 4: ...numbers followed by a K to indicate a conformal coating option IEC Hazardous Location Approval The following applies to products with IECEx certification Are intended for use in areas in which explos...

Страница 5: ...e of the following 1734 TB or 1734 TBS POINT I O two piece terminal base which includes the 1734 RTB removable terminal block and 1734 MB mounting base 1734 TOP or 1734 TOPS POINT I O one piece termin...

Страница 6: ...locking screw to a vertical position This releases the locking mechanism Then lift straight up to remove Description Description 1 Module locking mechanism 6 Interlocking side pieces 2 Slide in writab...

Страница 7: ...the Removable Terminal Block proceed as follows 1 Insert the end opposite the handle into the base unit This end has a curved section that engages with the wiring base 2 Rotate the terminal block into...

Страница 8: ...2 Slide the base down allowing the interlocking side pieces to engage the adjacent installed unit 3 Press firmly to seat the base on the DIN rail until the base snaps into place 4 Verify that the DIN...

Страница 9: ...wiring while the field side power is on an electric arc can occur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before pro...

Страница 10: ...hannel 3 High Byte Input Channel 3 Low Byte Status Byte for Channel 1 Status Byte for Channel 0 OR UR HHA LLA HA LA CM CF OR UR HHA LLA HA LA CM CF Status Byte for Channel 3 Status Byte for Channel 2...

Страница 11: ...hing green Channel being calibrated Solid red No power or major channel fault Flashing red Channel at end of range 0 mA or 21 mA IMPORTANT The Input update rate and Step response for 1734 IE4C and 173...

Страница 12: ...nal base 1734 TB3 1734 TB3S wiring base assembly POINTBus current max 75 mA Power dissipation max 0 55 W 28 8V DC Thermal dissipation max 2 0 BTU hr 28 8V DC Supply voltage backplane 5V DC Supply volt...

Страница 13: ...e line DM and 2 kV line earth CM on power ports 2 kV line earth CM on shielded ports Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM 150 kHz 80 MHz Certifications Certification...

Страница 14: ...nt with Article 58 2 of Radio Waves Act Clause 3 Morocco Arr t minist riel n 6404 15 du 29 ramadan 1436 CCC CNCA C23 01 CNCA C23 01 CCC Implementation Rule Explosion Proof Electrical Products CCC 2020...

Страница 15: ...Rockwell Automation Publication 1734 IN032F EN P September 2022 15 POINT I O 4 Channel High Density Current Input Module Installation Instructions Notes...

Страница 16: ...equipment should be collected separately from any unsorted municipal waste Rockwell Automation Support Use these resources to access support information Documentation Feedback Your comments help us s...

Отзывы: