Rockwell Automation Publication 1734-IN032F-EN-P - September 2022

11

POINT I/O 4 Channel High Density Current Input Module Installation Instructions

Specifications

Network status

Off

Device is not online:

- Device has not completed dup_MAC-id test.

- Device not powered – check module status indicator.

Flashing green

Device is online but has no connections in the established state.

Green

Device is online and has connections in the established state.

Flashing red

One or more I/O connections are in timed-out state.

Red

Critical link failure – failed communication device. Device detected error that prevents it from communicating on the network.

Flashing red/green

Communication faulted device – the device has detected a network access error and is in communication faulted state. 

Device has received and accepted an Identity Communication Faulted Request – long protocol message.

Channel status

Off

Module in CAL mode.

Solid green

Normal (channel scanning inputs).

Flashing green

Channel being calibrated.

Solid red

No power or major channel fault.

Flashing red

Channel at end of range (0 mA or 21 mA).

IMPORTANT

The Input update rate and Step response for 1734-IE4C and 1734-IE4CK modules differ from that of catalog number 1734-IE2C and 1734-IE2CK 

modules.

Input Specifications

Attribute

Value

Number of inputs

4, single-ended, non-isolated, current

Resolution

16 bits – over 0…21 mA

0.32 µA/cnt

Input current terminal

4…20 mA

0…20 mA

Absolute accuracy

(1)

Current terminal

0.1% Full Scale @ 25 °C

Accuracy drift w/ temp.

Current terminal

30 ppm/°C

Input update rate, per module

240 ms @ Notch = 50 Hz

200 ms @ Notch = 60 Hz (default)

120 ms @ Notch = 100 Hz

100 ms @ Notch = 120 Hz

60 ms @ Notch = 200 Hz

50 ms @ Notch = 240 Hz

40 ms @ Notch = 300 Hz

30 ms @ Notch = 400 Hz

25 ms @ Notch = 480 Hz

Step response, per channel

60 ms @ Notch = 50 Hz

50 ms @ Notch = 60 Hz (default)

30 ms @ Notch = 100 Hz

25 ms @ Notch = 120 Hz

15 ms @ Notch = 200 Hz

12.5 ms @ Notch = 240 Hz

10 ms @ Notch = 300 Hz

7.5 ms @ Notch = 400 Hz

6.25 ms @ Notch = 480 Hz

Input impedance/resistance

60 

Ω

Conversion type

Delta Sigma

Common mode rejection ratio

-120 dB

Table 1 - Indicator Status for Module (Continued)

Indicator

State

Description

Содержание Allen-Bradley POINT I/O 1734-IE4C

Страница 1: ...ubstantive updates only and is not intended to reflect all changes Topic Page Summary of Changes 1 Before You Begin 5 Install the Mounting Base 6 Install the Module 7 Install the Removable Terminal Bl...

Страница 2: ...ocumento ed i documenti elencati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell apparecchiatura Gli utenti devono leggere e comprendere le istruzion...

Страница 3: ...are suitable for use in Class I Division 2 Groups A B C D Hazardous Locations and nonhazardous locations only Each product is supplied with markings on the rating nameplate indicating the hazardous l...

Страница 4: ...numbers followed by a K to indicate a conformal coating option IEC Hazardous Location Approval The following applies to products with IECEx certification Are intended for use in areas in which explos...

Страница 5: ...e of the following 1734 TB or 1734 TBS POINT I O two piece terminal base which includes the 1734 RTB removable terminal block and 1734 MB mounting base 1734 TOP or 1734 TOPS POINT I O one piece termin...

Страница 6: ...locking screw to a vertical position This releases the locking mechanism Then lift straight up to remove Description Description 1 Module locking mechanism 6 Interlocking side pieces 2 Slide in writab...

Страница 7: ...the Removable Terminal Block proceed as follows 1 Insert the end opposite the handle into the base unit This end has a curved section that engages with the wiring base 2 Rotate the terminal block into...

Страница 8: ...2 Slide the base down allowing the interlocking side pieces to engage the adjacent installed unit 3 Press firmly to seat the base on the DIN rail until the base snaps into place 4 Verify that the DIN...

Страница 9: ...wiring while the field side power is on an electric arc can occur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before pro...

Страница 10: ...hannel 3 High Byte Input Channel 3 Low Byte Status Byte for Channel 1 Status Byte for Channel 0 OR UR HHA LLA HA LA CM CF OR UR HHA LLA HA LA CM CF Status Byte for Channel 3 Status Byte for Channel 2...

Страница 11: ...hing green Channel being calibrated Solid red No power or major channel fault Flashing red Channel at end of range 0 mA or 21 mA IMPORTANT The Input update rate and Step response for 1734 IE4C and 173...

Страница 12: ...nal base 1734 TB3 1734 TB3S wiring base assembly POINTBus current max 75 mA Power dissipation max 0 55 W 28 8V DC Thermal dissipation max 2 0 BTU hr 28 8V DC Supply voltage backplane 5V DC Supply volt...

Страница 13: ...e line DM and 2 kV line earth CM on power ports 2 kV line earth CM on shielded ports Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM 150 kHz 80 MHz Certifications Certification...

Страница 14: ...nt with Article 58 2 of Radio Waves Act Clause 3 Morocco Arr t minist riel n 6404 15 du 29 ramadan 1436 CCC CNCA C23 01 CNCA C23 01 CCC Implementation Rule Explosion Proof Electrical Products CCC 2020...

Страница 15: ...Rockwell Automation Publication 1734 IN032F EN P September 2022 15 POINT I O 4 Channel High Density Current Input Module Installation Instructions Notes...

Страница 16: ...equipment should be collected separately from any unsorted municipal waste Rockwell Automation Support Use these resources to access support information Documentation Feedback Your comments help us s...

Отзывы: