22
Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019
Second Generation MobileView Tethered Operator Terminal
Illuminated E-stop Button Brightness
See
for where to find the illuminated E-stop button on the junction box
circuit board.
See
for how to set the brightness of a second generation MobileView terminal meant to
attach to your 2711T-JBI65MI junction box.
Mount the IP65 Junction Box to Its Back Plate
To mount an IP65 junction box to its back plate,
perform the following steps.
1.
If you temporarily mounted the IP65
junction box as detailed in
Mount the IP65 Junction Box on page 15
,
remove the junction box from the screw
bosses.
2.
Align the IP65 junction box with its
mounted back plate.
3.
Mount the junction box to its back plate with the six supplied screws.
Torque the six screws to 0.85…1.15 N•m (7.5…10.2 lb•in).
Connect M12 On-Machine Connectors to the 2711T-JBIP65DM1 Junction Box
To connect M12 On-Machine connectors to the 2711T-JBIP65DM1 junction box, perform the
following steps.
1.
Determine where to connect each M12 On-Machine connection.
IMPORTANT
To maintain a tight seal and the IP65 rating, verify that the junction box is seated
properly to the cover plate.
Item
No.
Connector
Description
M12 Connector Type
1
Ethernet I/O
D-code pin female
2
Dry contact
5 pin micro-style male
3
Enabling device
5 pin I/O male
4
Control power
Mini 4 pin male
5
E-stop
5 pin I/O male
1
2
3
5
4
1