Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019
Second Generation MobileView Tethered Operator Terminal
Figure 5 - 2711T-JBIP65DC1 Junction Box Cable Outlets (with cover plate removed)
4.
Place the corresponding seal rings over each wire.
5.
Place the corresponding cable gland over each wire.
6.
Feed each wire through the corresponding cable outlet.
7.
See
for where to attach each wire to the appropriate terminal.
8.
After all wires are attached, hand-tighten the cable glands to secure the wires.
IMPORTANT
To maintain the protection class, any unused cable outlet must be sealed with a
black plug.
Item
No.
Cable Outlet
Description
Gland
Size
Cable Dia. Range
Protection
Class
1
Standard
M16 x 1.5
4…10 mm
(0.16…0.4 in.)
IP68
2
Standard
3
Ethernet
M20 x 1.5
3…6 mm
(0.12…0.24 in.)
IP66
4
Ethernet
5
Standard
M16 x 1.5
4…10 mm
(0.16…0.4 in.)
IP68
6
Standard
1
2
6
5
3
4
Black Plug
Cable Gland
1
2
3
5
4
6