Installation Instructions

Original Instructions

MegaDySC Dynamic Voltage Sag Corrector 

Bulletin Number 1608M—400 Amp Models sold after 1/1/2016 

Product Overview

The Allen-Bradley® Bulletin 1608M MegaDySC® Dynamic Sag Corrector is engineered to provide years of voltage sag (dip) protection. The 
patented DySC® technology does not use batteries, requires only routine maintenance, includes three-stage transient voltage surge suppression, and 
has unparalleled energy efficiency. Most electronic devices found in industry today are susceptible to power disturbances. A momentary sag in line 
voltage can reset or damage sensitive production equipment. The MegaDySC system provides instantaneous dynamic sag correction to help your 
equipment ride through these common events. It connects normal utility power directly to the load until a voltage sag occurs. During a sag, the 
MegaDySC inverter is activated-adding missing voltage to keep the load voltage within the normal range. When utility power returns to normal, the 
inverter is deactivated and the system is quickly ready to correct the next sag. 

The system reports these voltage sag events through its integrated touch screen display and provides system status, voltage sag notification and 
history, runtime statistics and system history in a simple and intuitive touch-based user interface.

Topic Page

Product Overview

1

Safety Considerations

3

Installation

3

Communication

10

Applying Power

13

Specifications

14

Содержание Allen-Bradley MegaDySC 1608M Series

Страница 1: ...equipment The MegaDySC system provides instantaneous dynamic sag correction to help your equipment ride through these common events It connects normal utility power directly to the load until a volta...

Страница 2: ...ncati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell apparecchiatura Gli utenti devono leggere e comprendere le istruzioni di installazione e cablag...

Страница 3: ...nment freeofconductive contaminants Avoid installing the MegaDySC system directly near heat emitting equipment such as ovens heaters or furnaces Ambient temperature must not exceed 40 C 104 F Do not o...

Страница 4: ...mic Voltage Sag Corrector SystemLayout Figure 1 Standard Run SR System Layout 12 7 21 5 1 29 723 2 81 7 6 5 48 5 25 167 7 21 6 7 2 5 167 7 21 5 7 6 5 1 5 1 6 12 7 21 6 3 66 167 7 21 5 48 5 25 5 48 5 2...

Страница 5: ...ic Voltage Sag Corrector Figure 2 Extended Run ER System Layout 12 7 21 5 1 29 723 2 81 7 6 5 48 5 25 167 7 21 5 7 1 581 5 7 6 5 48 5 25 5 1 5 48 5 25 02 8 12 7 21 6 5 1 6 7 2 5 167 7 21 167 7 21 6 3...

Страница 6: ...must be to the right of the Automatic Bypass section when viewed from the front of the system The DySC 400A Module MegaDySC section is shipped separately from the Automatic Bypass switchboard The Meg...

Страница 7: ...t This cable harness is routed through two large holes one in the ABP cabinet and one in the MegaDySC cabinet at the bottom front of the cabinets The harness is plugged into the associated terminal bl...

Страница 8: ...the control cable harness from the lower front switchboard pan into the MegaDySC section through the matching holes in the lower front side panels Install the 3 5 snap in grommet so that it protrudes...

Страница 9: ...21 25 87 7 1387 287387 5 029 723 3 1 72 5 1 25 381 175 5 21 6 520 520 5 5 520 7 7 51 7 27720 175 5 21 25 87 7 1387 287387 6 7 6 0 6 723 3 1 37 7 225 3 1 6 127 5 029 87 7 1387 0 0 3 5 3 6 287387 72 35...

Страница 10: ...tor Communication on page 12 MegaDySCSystemInterconnectionsChecklist Connect the Automatic Bypass ABP Switchboard to MegaDySC ground cable to the vertical strut in the MegaDySC cabinet at the location...

Страница 11: ...open removing power from the MegaDySC cabinet voltage sag correction will then be disabled This feature can be used as an Emergency Power Off EPO function for the MegaDySC cabinet Power to the output...

Страница 12: ...pass switchboard and is pre wired to monitor the MegaDySC input and output voltages The i Sense Ethernet and Modem communication ports are internally connected to the RJ45 and RJ11 jacks respectively...

Страница 13: ...ut power in the sequence OFF ON OFF ON within a one minute period will cause a Limit Cycle Timeout alarm In such case sag correction will be disabled for one minute after which the alarm will automati...

Страница 14: ...t rated for DC loads max allowable 2 DC loading Voltage Waveform Sine wave Voltage Sag Correction Times Single Event 3 phase 87 to 50 voltage remaining 5 s All three phases to zero voltage remaining 5...

Страница 15: ...Heat Loss Btu h Efficiency 480V SR 2421 8270 99 480V ER 2852 9740 99 380V SR 2321 7925 99 380V ER 2624 8960 99 3 wire 4 wire SR ER MegaDySC MegaDySC ER Weight Automatic Bypass Switchboard Weight Total...

Страница 16: ...We Doing form at http literature rockwellautomation com idc groups literature documents du ra du002_ en e pdf Technical Support Center Knowledgebase Articles How to Videos FAQs Chat User Forums and P...