Troubleshooting the Kinetix 6000 Drive System
151
E79
DriveOvervoltage
Fault
(Shunt Module Flt)
Shunt module temperature fault LED indicator is steady red.
Refer to Temperature Fault LED Indicator
on page 154.
Shunt module shunt fault LED indicator is steady red.
Refer to Shunt Fault LED Indicator on page
154.
Module missing from power rail.
• Install missing module on power rail.
• Fill empty slot with slot filler module.
E80
DriveHardFault
(CPLD Flt)
Control hardware fault detected.
Replace module.
E81
DriveHardFault
(Common Bus Flt)
Follower IAM detected ac input power being applied.
Remove ac input power connections from
follower IAM.
E90
DriveHardFault
(Pre-charge Timeout Flt)
Pre-charge resistor power exceeds the resistor rating.
Allow resistor to cool.
All
others
RESERVED
Call your local Rockwell Automation sales
representative.
Error
Code
Fault Message
RSLogix
(HIM)
Problem or Symptom
Potential Cause
Possible Resolution
Содержание Allen-Bradley Kinetix 6000
Страница 8: ...Publication 2094 UM001A EN P September 2006 8 Table of Contents...
Страница 18: ...Publication 2094 UM001A EN P September 2006 18 Start...
Страница 118: ...Publication 2094 UM001A EN P September 2006 118 Connecting the Kinetix 6000 Drive System...
Страница 144: ...Publication 2094 UM001A EN P September 2006 144 Configure and Startup the Kinetix 6000 Drive System...
Страница 168: ...Publication 2094 UM001A EN P September 2006 168 Removing and Replacing the Kinetix 6000 Drive Modules...
Страница 190: ...Publication 2094 UM001A EN P September 2006 190 Specifications and Dimensions...
Страница 256: ...Publication 2094 UM001A EN P September 2006 256 Integrating Resistive Brake Modules with Kinetix 6000 Drives...
Страница 265: ...Publication 2094 UM001A EN P September 2006 265 Notes...
Страница 266: ...Publication 2094 UM001A EN P September 2006 266 Notes...
Страница 267: ...Publication 2094 UM001A EN P September 2006 267 Notes...