Rockwell Automation Publication 440L-IN012A-EN-P - November 2017

GuardShield Type 4 and GuardShield Remote Teach

System Delivery

The GuardShield Remote Teach light curtain system is delivered with 

the GuardShield light curtain transmitter and receiver that is already 

configured in the standard GuardShield light curtain operating mode of 

“Guard Only.” This mode is Automatic reset and all features not 

activated.
The 2 m (6.56 ft) patchcord (889D-F4ACDM-2), Remote Teach 

(440L-M8600) key selector switch box and mounting hardware are 

packaged with each GuardShield Remote Teach light curtain system 

(see 

Table 62 on page 31

) along with a standard GuardShield light 

curtain transmitter and remote teach receiver.

Remote Teach Box

Key Switch Positions

The GuardShield remote teach light curtain box uses a Rockwell 

Automation® 800FM series, three-position IP66 rated spring-loaded key 

selector switch. There are three key selector switch positions on the 

GuardShield Remote Teach light curtain box.

• RUN: This key selector switch position is required for the 

GuardShield light curtain to operate in its normal operating 

mode. 

• CONFIGURE: This key selector switch position simulates the 

opening of the GuardShield light curtain DIP switch door. This 

position sends a signal to the GuardShield light curtain 

firmware to change from the RUN mode of operation to a 

configuration mode of operation. In this mode, all outputs are 

in the OFF state.

• TEACH: This key selector switch position performs the 

function of changing the operating mode configuration of the 

GuardShield light curtain. 

Figure 61 - Key Selector Switch Label Positions

System Installation

The GuardShield light curtain transmitter and receiver are properly 

mounted to the machinery to be guarded per the GuardShield Light 

Curtain Installation Instructions. 
After aligning the GuardShield safety light curtains and attaining a 

“green” state, the safety light curtain is transmitting infrared light and 

the receiver OSSDs are high. It is now possible to reconfigure the 

GuardShield light curtain.
Use the T8 TORX® bit supplied with each GuardShield light curtain 

bracket kit to open the GuardShield light curtain Receiver door and set 

DIP switch four to the ON position. This DIP switch allows the 

activation and configuration of a monitored fixed blanked area within 

the GuardShield light curtain protective height. 
Make any additional DIP switch settings now.

Remote Teach Procedure

1. Position object in the GuardShield light curtain sensing field, 

confirm that the synchronization beam is not obstructed

2. Turn key selector switch to the configure position. The red 

status indicator on the receiver flashes and the yellow blanking 

status indicator is illuminated. 

3. Turn and hold key selector switch in the Teach position
4. The GuardShield light curtain receiver yellow blanking status 

indicator begins to flash.

5. When the yellow blanking status indicator stops flashing, 

release the key selector switch to the configure position within 

two seconds.

6. The GuardShield light curtain receiver yellow blanking status 

indicator flashes three times to confirm that the new fixed 

blanking configuration has been set.

7. Turn the key selector switch to the RUN position, the green 

status indicator on the GuardShield light curtain receiver 

illuminates.

8. Use the supplied test rod to confirm the fixed blanking area and 

any other settings are configured as expected.

It is possible to configure and activate both fixed and one or two beam 

floating blanking on the GuardShield light curtain. 

IMPORTANT

If EDM or Reset functions are to be configured through DIP 

switch settings, assure that the proper receiver wire 

connections are made.
It is not possible to blank out the synch beam, which is the 

first beam adjacent to the GuardShield light curtain 

diagnostic status indicators.
If the transmitter configuration needs to be changed from the 

factory settings, set the DIP switches in the transmitter and 

follow the standard teach process.

IMPORTANT

Once the GuardShield light curtain is configured by changing 

factory DIP switch positions and performing the Teach 

function (see 

Teach-in Procedure Function on page 18

), the 

GuardShield light curtain will be reconfigured. Any future 

Teach procedure will only change the configuration of the 

fixed blanking area. 
After teaching the GuardShield light curtain a new 

configuration, confirm that the configuration that was 

expected to be configured has actually been configured.
Fixed blanking creates a “hole” in the detection area of the 

GuardShield light curtain. It is necessary to assure that access 

to the hazard being protected against is prevented by means 

of barrier guarding. It should not be possible to access the 

hazard through the fixed blanked area.

Содержание Allen-Bradley Guardmaster GuardShield Remote Teach

Страница 1: ...nt of operation and perimeter and access detection It is a self contained two box Type 4 electro sensitive protective equipment ESPE with DIP switch selectable operating modes The GuardShield light cu...

Страница 2: ...e is a Type 4 ESPE as defined by IEC 61496 1 and IEC 61496 2 Therefore it is allowed for use with controls In safety Cat 4 up to PLe in accordance with EN ISO 13849 1 SIL CL3 in accordance with EN 620...

Страница 3: ...ation removes the possibility of operation by a person working inside the hazardous area The statutory and local rules and regulations must be observed when installing and using the device Restart int...

Страница 4: ...segments The individual segments can have mixed resolutions for instance 14 mm and 30 mm 1 18 in as long as the pairs have the same protective heights and resolutions Cascade segments can be used as...

Страница 5: ...eration is through DIP switch setting in the GuardShield light curtain receiver see Table 37 on page 17 EDM is not available in the middle and end segments of a cascading GuardShield light curtain sys...

Страница 6: ...d activated FloatingBlanking The floating blanking mode of operation is activated through DIP switch settings that are located in the GuardShield light curtain receiver see Receiver Factory Settings o...

Страница 7: ...ing Blanking Symbol Description Beam not interrupted Beam interrupted Beamisactivated forFixedBlanking andnot interrupted Beamisactivated forFixedBlanking andinterrupted Case 1 2 3 4 5 6 7 8 Infrared...

Страница 8: ...ime that is measured at approximately the 90 position of the crankshaft rotation Resolution Protective Height Number of Beams ResponseTime w o Coding ResponseTime w Coding 14 0 55 160 6 3 16 20 ms 30...

Страница 9: ...object sensitivity of the safety light curtain Object sensitivity resolution is the smallest diameter object which is detected anywhere in the sensing field Example for US In a perpendicular safety l...

Страница 10: ...between sender and receiver Figure 12 Minimum Distance from Reflecting Surfaces Howto DeterminetheMinimumDistancefromtheReflecting Surfaces Determine the distance D m sender receiver Read the minimum...

Страница 11: ...L ALAT and mounting bracket 450L ALAT C is offered as an accessory for aligning the GuardShield light curtain without Integrated Laser Alignment see Laser Alignment Tool on page 35 AlignmentProceduref...

Страница 12: ...ective solution is to interconnect an additional light curtain in series to the vertical pair Select a Host or cascade pair of GuardShield safety light curtains with a protective height and resolution...

Страница 13: ...ry to use additional brackets see Figure 23 to mount the GuardShield light curtain at a proper safety distancefromthe machinery hazard Forapplications with shock and or vibrations also see Table 66 Fi...

Страница 14: ...Low Voltage Directives The grounded conductor of the power supply device must be connected to a grounded conductor PE The maximum deviation of the voltage levels is 24V DC 20 EDMConnection See Relay...

Страница 15: ...ter Brown 1 24V DC White 2 No Connection Blue 3 0VDC Black 4 MachineTestSignal Receiver Connection Face View of Female DC Micro Color PinNo Signal Receiver White 1 Auxiliary Output Brown 2 24V DC Gree...

Страница 16: ...le IMPORTANT IfMPCE EDMisactivated intheGuardShieldlightcurtain the application requires asafety contactor If MPCE EDMis not used K1 K2 can bestandardcontactors M 24V DC 24V Ground SENDER OSSD 1 OSSD...

Страница 17: ...ton Switch Switch Function Default Setting Description 1 Mode Activation Combination activates oneofthe followingmodes Guardonly startinterlock restart interlock ON Guard Only see Table 39 on page17 2...

Страница 18: ...tep 2 Selectthe desiredDIPswitch setting Step 3 Press and hold theTeach button Theyellow status indicator startsflashing at 10 Hz 10x per second RX Blanking indicator TX Emitting indicator Step 4 Afte...

Страница 19: ...set mode in start orrestart interlock aligned 5 Fixed blankingmode aligned not ininterlock 6 FloatingorFloating Fixed Blanking mode aligned not in interlock 7 Transmitter testinputactive pin 4 8 Inter...

Страница 20: ...llowinginspection Improperinspectioncanlead to serious or even deadly injury 1 Approach to hazardous machineparts mustonly bepossiblethrough passagethrough the protectivefield ofGuardShieldlight curta...

Страница 21: ...XX M or4K R 02 M representedManchester NH replacedby 4KforMonterrey Mexico J 2004 K 2005 L 2006 M 2007 N 2008 P 2009 R 2010 S 2011 T 2010 U 2013 V 2014 W 2015 Y 2016 Z 2017 Rockwell Automation Inc 12...

Страница 22: ...ON state OSSDOFF state Blanking Alignment Interlock Constant ON whenOSSDis in ON state greenindicator Constant ON whenOSSDis in OFF state redindicator Lights upatinterruptionofprotective fieldor if f...

Страница 23: ...itter Receiver Resolution mm in No of Beams Protective Heights mm in PairWeight kg lb Finger Resolution 440L P4JL0320YD 440L T4JL0320YD 440L R4JL0320YD 14 0 55 32 320 12 59 5 17 2 35 440L P4JL0480YD 4...

Страница 24: ...35 440L C4J0480YD 440L G4J0480YD 440L F4J0480YD 14 0 55 48 480 18 89 6 59 2 99 440L C4J0640YD 440L G4J0640YD 440L F4J0640YD 14 0 55 64 640 25 19 7 99 3 62 440L C4J0800YD 440L G4J0800YD 440L F4J0800YD...

Страница 25: ...8 80 1600 62 99 19 28 8 75 Sensor Pair Transmitter Receiver Resolution mm in No of Beams Protective Heights mm in Pair Weight kg lbs Finger Resolution 440L C4JL0320YA 440L G4JL0320YA 440L F4JL0320YA 1...

Страница 26: ...ransmitter R Receiver Standard C Host Pair G Host Transmitter F Host Receiver Cascading Bulletin Number 0160 Protective Height 0320 0480 0960 1440 0640 1120 1600 0800 1280 1760 R Remote Teach Pigtail...

Страница 27: ...28 5 632 1 5 24 9 0 06 440L 4 0640Y 640 0 5 25 2 0 02 756 29 8 792 1 5 31 2 0 06 440L 4 0800Y 800 0 6 31 5 0 02 916 36 1 952 1 5 37 5 0 06 440L 4 0960Y 960 0 6 37 8 0 02 1076 42 4 1112 1 5 43 8 0 06...

Страница 28: ...9 686 26 6 712 28 0 440L 1 4 2 L0640Y 3 640 25 2 836 32 9 872 34 3 440L 1 4 2 L0800Y 3 800 31 5 996 39 2 103 4 1 440L 1 4 2 L0960Y 3 960 37 8 1156 45 5 119 4 7 440L 1 4 2 L1120Y 3 1120 44 1 1316 51 8...

Страница 29: ...supplied with each GuardShield Remote Teach light curtain receiver The GuardShield Remote Teach Box light curtain system consists of Remote teach key selector switch box with mounting plate and two k...

Страница 30: ...vation and configuration of a monitored fixed blanked area within the GuardShield light curtain protective height Make any additional DIP switch settings now RemoteTeachProcedure 1 Position object in...

Страница 31: ...stem 1600 mm 63 in protectiveheight 30 mm 1 18 in resolution 440L S4K1760YR GuardShield RemoteTeachlight curtain system 1760 mm 69 3 in protectiveheight 30 mm 1 18 in resolution Catalog Number Descrip...

Страница 32: ...GWS0800 440L AGWS0960 440L AGWS1120 440L AGWS1280 440L AGWS1440 440L AGWS1600 440L AGWS1760 GuardShield light curtainTest Rod 14 mm 450L AT 14 GuardShield light curtainTest Rod 30 mm 450L AT 30 GuardS...

Страница 33: ...0 mm 70 86 in 15 m 49 21 ft 1896 1840 1872 1940 8 x 13 50 1 96 73 2 87 A Ls L B A A Section A A 120 114 4 48 13 3 5 24 35 1 37 54 2 12 44 4 1 74 75 2 95 2 5 0 09 6 5 0 25 4 5 0 17 10 5 0 41 Model No S...

Страница 34: ...40L P2K 0480YD 440L P4A2500YD 440L AM0750600 440L AM1250600 440L P4 0640Y 440L P2K 0640YD 440L AM0750750 440L AM1250750 440L P4 0800Y 440L P2K 0800YD 440L AM0750900 440L AM1250900 440L P4 0960Y 440L P...

Страница 35: ...GuardShield light curtain transmitter host patchcord has 4 pin DC micro over molded quick disconnect connectors that are offered in lengths of 0 3 m 0 98 ft 1 m 3 28 ft and 2 m 6 56 ft The GuardShiel...

Страница 36: ...CDM 1 5 pin M12 patchcord 1 3 28 5 6 7 8 4 3 1 2 889D F5ACDM 2 5 pin M12 patchcord 2 6 56 889D F5ACDM 5 5 pin M12 patchcord 5 16 4 889D F5ACDM 10 5 pin M12 patchcord 10 32 81 IMPORTANT Transmitter and...

Страница 37: ...o and including SIL cl3 in accordance with EN 61508 and EN 62061 Performance Level e and Category 4 in accordance with ISO 13849 1 ESPE Type 4 safety light curtain in accordance with EN IEC 61496 Comp...

Страница 38: ...38 Rockwell Automation Publication 440L IN012A EN P November 2017 GuardShieldType 4and GuardShield RemoteTeach Notes...

Страница 39: ...Rockwell Automation Publication 440L IN012A EN P November 2017 39 GuardShieldType 4andGuardShield RemoteTeach Notes...

Страница 40: ...ent complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents du ra du002_ en e pdf Technical Support Center KnowledgebaseArticles How toVideos FAQs...

Отзывы: