Communicating with Devices on an EtherNet/IP Link
6-3
Assigning Network Parameters with BOOTP/DHCP
The EtherNet/IP Option board ships with BOOTP enabled. You must assign
an IP address to the Ethernet port in order for the controller to communicate
over an EtherNet/IP network.
The BOOTP/DHCP utility is a stand alone program that is located in the:
•
BOOTP-DHCP Server folder in the Rockwell Software program folder
on the Start menu (the utility is automatically installed when you install
RSLinx software)
•
Tools directory on the RSLogix 5000 installation CD.
The computer running the BOOTP/DHCP utility and the DriveLogix5730
controller must be on the same EtherNet/IP network.
To use the BOOTP/DHCP utility:
1.
Start the BOOTP/DHCP software.
2
.
From the Tools menu, select Network Settings.
Click OK.
3.
Enter the required data.
Note: If you have not run the BOOTP/DHCP program before,
it will automatically launch the Network Settings window.
Содержание Allen-Bradley DriveLogix 5730
Страница 6: ...4 ...
Страница 10: ...p 4 Notes ...
Страница 22: ...1 12 What is DriveLogix5730 Notes ...
Страница 68: ...3 20 Placing and Configuring Local I O Notes ...
Страница 131: ...Communicating with Devices on an EtherNet IP Link 6 33 This example shows DriveLogix1 producing tagA and consuming tagB ...
Страница 134: ...6 36 Communicating with Devices on an EtherNet IP Link Notes ...
Страница 155: ...Communicating with Devices on an ControlNet Link 7 21 This example shows DriveLogix1 producing tagA and consuming tagB ...
Страница 182: ...9 10 Communicating with Devices on a DH485 Link Notes ...
Страница 200: ...B 10 Access Procedures Notes ...
Страница 205: ......
Страница 206: ......
Страница 207: ......
Страница 209: ...Allen Bradley User Manual DriveLogix 5730 ...