Publication 1756-UM001A-EN-P - September 2000
Communicate with 1756 I/O
4-7
F.
Select a
Comm Format
:
IMPORTANT
If the module is also in the I/O configuration of
another controller, then select the
Listen Only
version
of the Comm Format (e.g.,
Listen Only - Input Data
).
If this module is a:
And:
And you want to:
Then select:
diagnostic digital input
Full Diagnostics - Input Data
non-diagnostic digital input
local chassis
time stamp a change in data
CST Timestamped Input Data
omit time stamps
Input Data
remote chassis
Rack Optimization
diagnostic digital output
schedule when to apply outputs
Full Diagnostics - Scheduled
Output Data
not schedule when to apply
outputs
Full Diagnostics - Output Data
fused digital output
schedule when to apply outputs
CST Timestamped Fuse Data -
Scheduled Output Data
not schedule when to apply
outputs
CST Timestamped Fuse Data -
Output Data
non-diagnostic and non-fused
digital output
local chassis
schedule when to apply outputs
Scheduled Output Data
not schedule when to apply
outputs
Output Data
remote chassis
Rack Optimization
non-isolated analog input
floating point mode provides
sufficient sample time
time stamp when the data is
sampled
CST Timestamped Float Data -
wiring_mode
omit the time stamp
Float Data -
wiring_mode
floating point mode
does not
provide sufficient sample time
time stamp when the data is
sampled
CST Timestamped Integer Data -
wiring_mode
omit the time stamp
Integer Data -
wiring_mode
isolated or temperature
measuring analog input
25 ms sample time or greater is
sufficient
time stamp when the data is
sampled
CST Timestamped Float Data
omit the time stamp
Float Data
sample time must be less than
25 ms
time stamp when the data is
sampled
CST Timestamped Integer Data
omit the time stamp
Integer Data
analog output
associated inputs are REALs
time stamp the data echo
CST Timestamped Float Data
omit the time stamp
Float Data
associated inputs are INTs
time stamp the data echo
CST Timestamped Integer Data
omit the time stamp
Integer Data
Содержание Allen-Bradley ControlLogix 1756-L Series
Страница 1: ...ControlLogix System 1756 Lx User Manual ...
Страница 10: ...Publication 1756 UM001A EN P September 2000 Table of Contents vi ...
Страница 64: ...Publication 1756 UM001A EN P September 2000 4 16 Communicate with 1756 I O Notes ...
Страница 90: ...Publication 1756 UM001A EN P September 2000 6 16 Communicate with 1794 I O Over a ControlNet Network Notes ...
Страница 108: ...Publication 1756 UM001A EN P September 2000 7 18 Communicate with Another Controller over a ControlNet Network Notes ...
Страница 112: ...Publication 1756 UM001A EN P September 2000 8 4 Route PLC 5 Messages Between ControlNet Networks Notes ...
Страница 119: ...Publication 1756 UM001A EN P September 2000 Communicate with a PanelView Terminal Over a ControlNet Network 9 7 ...
Страница 152: ...Publication 1756 UM001A EN P September 2000 11 4 Monitor Connections Notes ...
Страница 160: ...Publication 1756 UM001A EN P September 2000 12 8 Communicate with a DeviceNet Device Notes ...
Страница 188: ...Publication 1756 UM001A EN P September 2000 14 8 Route PLC 5 or SLC 500 Messages From a DH Network Notes ...
Страница 204: ...Publication 1756 UM001A EN P September 2000 15 16 Communicate Over a Remote I O Network Notes ...
Страница 232: ...Publication 1756 UM001A EN P September 2000 18 18 Configure DF1 Master and Slave Communications Notes ...
Страница 266: ...Publication 1756 UM001A EN P September 2000 21 10 Maintain the Battery Notes ...
Страница 286: ...Publication 1756 UM001A EN P September 2000 B 18 Estimate Execution Time Notes ...
Страница 300: ...Publication 1756 UM001A EN P September 2000 C 14 Estimate Memory Use Notes ...
Страница 305: ......
Страница 307: ...ControlLogix System User Manual ...