66
Rockwell Automation Publication 856T-UM001B-EN-P - April 2021
Appendix C Device Parameters
Process Data Input
The 856T-B24LC module transmits the following Process Input Data to the
master each cycle.
The total size of data is 48 bits where Alarm status word is at the most
significant position of the Data process Input.
•
Class B Voltage bits [7:0] - The IO-Link module maintains 8-bit value that
represents the Class B power supply voltage. This value is Read-only via
the IO-Link protocol.
•
Class A Voltage bits [15:8] - The IO-Link module maintains 8-bit value
that represents the Class A power supply voltage. This value is Read-only
via the IO-Link protocol.
•
Internal temperature [23:16] - The internal temperature of the IO-Link
module is provided as part of the process data input.
•
Circuit Status [31:24]- The IO-Link module provides the control circuit
status of the unit as part of the process data input.
•
Alarm Status [47:32] - The 856T-B24LC module provides the alarm status
of the unit as part of the process input data.
for a detailed view of the bits for each of the fields in the
Process Data Input.
Reset Counter Circuit 1
0x0002/2
0x00A0/160
Write-only
—
Reset the ON/OFF counter for
Circuit 1
UIntegerT
(bit length = 8)
Reset Counter Circuit 2
0x00A1/161
Write-only
Reset the ON/OFF counter
for
Circuit
2
UIntegerT
(bit length = 8)
Reset Counter Circuit 3
0x00A2/162
Write-only
Reset the ON/OFF counter
for
Circuit
3
UIntegerT
(bit length = 8)
Reset Counter Circuit 4
0x00A3/163
Write-only
Reset the ON/OFF counter
for
Circuit
4
UIntegerT
(bit length = 8)
Reset Counter Circuit 5
0x00A4/164
Write-only
Reset the ON/OFF counter
for
Circuit
5
UIntegerT
(bit length = 8)
Reset Counter Circuit 6
0x00A5/165
Write-only
Reset the ON/OFF counter
for
Circuit
6
UIntegerT
(bit length = 8)
Reset Counter Circuit 7
0x00A6/166
Write-only
Reset the ON/OFF counter
for
Circuit
7
UIntegerT
(bit length = 8)
Start Calibration
0x00A7/167
Write-only
Starts the calibration of the
accelerometer max thresholds.
Returns success immediately
UIntegerT
(bit length = 8)
Stop calibration
0x00A8/168
Write-only
Cancels the calibration of the
accelerometer. Returns success
immediately
UIntegerT
(bit length = 8)
Reset All Statistics
0x00AA/170
Write-only
Resets all circuit counters back to
default value as well as Maximum
Vibration Since Power Up, Min
Module Temperature since Power
up and Max Module Temperature
since power up
UIntegerT
(bit length = 8)
Table 17 - IO-Link System Commands
Command Name
Index
(Hex/Dec)
Command
(Hex/Dec)
Access
Default Value
Description
Data Type
(Length, Offset)
Table 18 - Process Data Input
[47:32]
[31:24]
[23:16]
[15:8]
[7:0]
Alarm Status
Circuit Status
Internal Temperature
Class A Voltage
Class B Voltage
Содержание Allen-Bradley 856T-B24LC
Страница 6: ...6 Rockwell Automation Publication 856T UM001B EN P April 2021 Table of Contents Notes ...
Страница 18: ...18 Rockwell Automation Publication 856T UM001B EN P April 2021 Chapter 2 IO Link Overview Notes ...
Страница 72: ...72 Rockwell Automation Publication 856T UM001B EN P April 2021 Appendix D Device Status Notes ...
Страница 76: ...76 Rockwell Automation Publication 856T UM001B EN P April 2021 Appendix F Troubleshooting Notes ...
Страница 80: ...80 Rockwell Automation Publication 856T UM001B EN P April 2021 Index Notes ...