48
Rockwell Automation Publication 7712-UM001D-EN-P - October 2017
Chapter 5
Maintenance
Figure 29 - Establishing Contact Gap
6. Install the load terminal retaining bolts at the rear of the contactor.
Leave the load terminal nuts loose for fine adjustment of the overtravel
and contact gap.
7. Install the vacuum bottle mounting bolts at the top of the contactor
(reverse of step
3
). Ensure the threads align to prevent cross-threading.
Hold the bottle to prevent it from turning while torquing the vacuum
bottle mounting bolts.
Calibrate the Overtravel and Contact Gap
1. Close the contactor by using the TEST control circuit in the starter.
Insert a feeler gauge of 0.065 in. (1.65 mm) into the overtravel gap of a
bottle assembly (
Figure 30
).
2. Rotate the insulator until the gap is correct. Repeat for the two
remaining bottles.
Figure 30 - Establishing Overtravel
IMPORTANT
This establishes synchronization between the three vacuum bottles.
0.190 in. [4.82 mm]
Vacuum Bottles
Insulator
Overtravel Gap
0.065 in. [1.65 mm]
Содержание Allen-Bradley 7712
Страница 6: ...6 Rockwell Automation Publication 7712 UM001D EN P October 2017 Table of Contents Notes ...
Страница 10: ...10 Rockwell Automation Publication 7712 UM001D EN P October 2017 Preface Notes ...
Страница 14: ...14 Rockwell Automation Publication 7712 UM001D EN P October 2017 Chapter 1 General Information Notes ...
Страница 24: ...24 Rockwell Automation Publication 7712 UM001D EN P October 2017 Chapter 3 Start up Procedure ...
Страница 25: ...Rockwell Automation Publication 7712 UM001D EN P October 2017 25 Start up Procedure Chapter 3 ...
Страница 26: ...26 Rockwell Automation Publication 7712 UM001D EN P October 2017 Chapter 3 Start up Procedure ...
Страница 36: ...36 Rockwell Automation Publication 7712 UM001D EN P October 2017 Chapter 4 Equipment Operation Notes ...
Страница 58: ...58 Rockwell Automation Publication 7712 UM001D EN P October 2017 Chapter 5 Maintenance Notes ...
Страница 73: ......