136
Rockwell Automation Publication 35-UM001A-EN-P - May 2022
Chapter 6 Safety Functions
Safety Input or Output Fault Recovery
If an error is detected, the safety data remains in the Off state. Follow this
procedure to activate the safety data again.
1. Remove the cause of the error.
2. Place the safety input or safety output into the safe state.
3. Allow the input- or output-error latch time to elapse.
After these steps are completed, the I/O indicator (red) turns Off. The
safety input or output data is now active.
Safety I/O Wiring
.
Safety Input Internal Wiring Diagram
IMPORTANT
Stuck high faults on safety outputs require a power reset to clear
the error.
IMPORTANT
The wiring examples that are shown here are not a guarantee of
Safety Category and Performance Level ratings. You must
perform your own risk assessment to validate the requirements
of your system.
Test Output 1
Safety Input 1
Input Common
Safety Input 0
Test Output 0
M12 5-Pin
Connector
Armor PowerFlex Drive Internal Circuitry
Unswitched 24V DC
Safety VCC_3V3
Safety VCC_3V3
Safety VCC_3V3
Safety VCC_3V3
In0 Monitor
In0 Test
Safety μC
B
Safety μC
A
In1 Monitor
In1 Test
Test 1
Test 0
Field Wiring
Unswitched 24V DC
Unswitched 24V DC
Unswitched 24V DC
Test Out 1
Circuit
Safe In1
Circuit
Safe In0
Circuit
Test Out 0
Circuit