Chapter 6 Troubleshoot the System
Alerts
The terminal displays alerts at times during operation. The alert consists of an
ID number and a description. Follow the corrective action to resolve the alert.
PanelView 800 Terminal Alerts
Category
ID
Description
Corrective Action
Communication
2
Data Access Error for Alias /*S:0 Param2*/, Controller /*S:0
Param3*/, Address is /*S:0 Param4*/, Communication Flag is /
*S:0 Param1*/
The terminal is having trouble reading the external tag at this
controller and address.
Check that the communication network cable is connected.
If new ladder logic is downloading to the controller, you could see
this message. After the download, communication should run
normally.
Verify you have good communication to the controller. If a remote
device not responding alert was present, then all external tags being
actively scanned will generate this alert.
Is the address configured in the controller? If so, make sure all
addresses of external tags to this controller are configured at the
controller. If one address is outside of the range, a block of
addresses might show this condition. If the address is configured as
write-only at the controller, this address cannot be read. Set this
external tag as write-only and remove panel devices from your
application that want to display data from this external tag.
Communication
3
Communication Server Error
Contact technical support providing this data. ID1-/*S:0 Param1*/,
ID2-/*S:0 Param2*/, P1-/*S:0 Param3*/
Reboot the terminal.
Communication
4
Communication Server Error
Contact technical support providing this data. ID1-/*S:0 Param1*/,
ID2-/*S:0 Param2*/, P1-/*S:0 Param3*/, P2-/*S:0 Param4*/
Reboot the terminal.
Communication
5
Communication Server Error
Contact technical support providing this data. ID1-/*S:0 Param1*/,
ID2-/*S:0 Param2*/, P1-/*S:0 Param3*/, P2-/*S:0 Param4*/, P3-/
*S:0 Param5*/
Reboot the terminal.
Communication
6
Communication Server Error
Contact technical support providing this data. ID1-/*S:0 Param1*/,
ID2-/*S:0 Param2*/, P1-/*S:0 Param3*/, P2-/*S:0 Param4*/, P3-/
*S:0 Param5*/, P4-/*S:0 Param6*/
Reboot the terminal.
Communication
7
Communication Server Error
Contact technical support providing this data. ID1-/*S:0 Param1*/,
ID2-/*S:0 Param2*/, P1-/*S:0 Param3*/, P2-/*S:0 Param4*/, P3-/
*S:0 Param5*/, P4-/*S:0 Param6*/, P5-/*S:0 Param7*/
Reboot the terminal.
Communication
8
Communication Server Error
Contact technical support providing this data. ID1-/*S:0 Param1*/,
ID2-/*S:0 Param2*/, P1-/*S:0 Param3*/, P2-/*S:0 Param4*/, P3-/
*S:0 Param5*/, P4-/*S:0 Param6*/, P5-/*S:0 Param7*/, P6-/*S:0
Param8*/
Reboot the terminal.
Communication
9
Communication Server Error
Contact technical support providing this data. ID1-/*S:0 Param1*/,
ID2-/*S:0 Param2*/
Reboot the terminal.
Communication
10
Write Error for Alias /*S:0 Param2*/, Controller /*S:0 Param3*/,
Address is /*S:0 Param4*/, Communication Flag is /*S:0
Param1*/
The terminal is having trouble writing the external tag at this
controller and address.
Verify you have good communication to the controller.
Verify that the communication network cable is connected.
If new ladder logic is downloading to the controller, you could see
this message. After the download, communication should run
normally.
If a remote device not responding alert is present, then all external
tags being written to will generate this alert.
Is the address configured in the controller? If the address is
configured as read-only at the controller, this address cannot be
written to. Set this external tag as read and remove panel devices
from your application that can write data to this external tag.
Communication
11
Read Error for Alias /*S:0 Param2*/, Controller /*S:0 Param3*/,
Address is /*S:0 Param4*/, Communication Flag is /*S:0
Param1*/
The terminal is having trouble reading the external tag at this
controller and address.
Verify you have good communication to the controller.
Verify that the communication network cable is connected.
If new ladder logic is downloading to the controller, you could see
this message. After the download, communication should run
normally.
If a remote device not responding alert was present, then all external
tags being read from will generate this alert.
Is the address configured in the controller? If the address is
configured as write-only at the controller, this address cannot be
read from. Set this external tag as write and remove panel devices
from your application that can read data from this external tag.
Содержание Allen-Bradley 2711R-T10T
Страница 8: ...8 Rockwell Automation Publication 2711R UM001H EN E April 2021 Table of Contents Notes...
Страница 16: ...16 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 1 Overview Notes...
Страница 44: ...44 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 2 Configure the Terminal Notes...
Страница 94: ...94 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 5 Virtual Network Computing Notes...
Страница 106: ...106 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 6 Troubleshoot the System Notes...
Страница 118: ...118 Rockwell Automation Publication 2711R UM001H EN E April 2021 Appendix B Upgrade Firmware Notes...
Страница 122: ...122 Rockwell Automation Publication 2711R UM001H EN E April 2021 Appendix C Install and Replace Components Notes...
Страница 156: ...156 Rockwell Automation Publication 2711R UM001H EN E April 2021 Index Notes...
Страница 157: ...Rockwell Automation Publication 2711R UM001H EN E April 2021 157 PanelView 800 HMI Terminals User Manual...