Rockwell Automation Publication 750-IN118A-EN-P - May 2021
69
Chapter 3 Mechanical and Electrical Installation
Figure 61 - Frame 8 Configured Input Bay with
Circuit Breaker, Top Entry: Internal Components
and Installation Connection Locations
Item Description
1
Roof exhaust vent with internal air filter
2
PE ground bar with ground clamps included. Terminating point to chassis ground for incoming AC line and
shield. Ground connections must be made during installation.
3
Terminal lugs for customer AC line input power. Connections must be made during installation.
4
Thermostat
5
AC line input protection circuit breaker
6
Terminal lugs to supply power to the drive input bay
7
Terminal blocks
8
Fuse blocks
9
Control relays
10
Control power supply (24V DC)
11
Uninterruptible power supply and battery (behind control power supply)
12
Control transformer
1
2
3
5
7
8
9
10
11
6
12
4