F-6
PID Set Up
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22B-UM001I-EN-E
Invert Function
For a 4-20mA signal, the following parameter settings are used so that a
20mA signal = 0% PID Reference and a 4mA signal = 100% PID
Reference.
•
A112 [Anlg In 4-20mA Lo] = 100.0%
•
A113 [Anlg In 4-20mA Hi] = 0.0%
•
A132 [PID Ref Sel] = 3 “4-20mA Input”
Alternatively, you can set the value of A167 [PID Invert Error] to 1 to
change the sign of the PID error. See
[PID Invert Error] in Chapter
3 for more details.
PID Deadband
Parameter A138 [PID Deadband] is used to set a range, in percent, of the
PID Reference that the drive will ignore.
Example
•
[PID Deadband] is set to 5.0
•
The PID Reference is 25.0%
•
The PID Regulator will not act on a PID Error that falls between 20.0
and 30.0%
0
10
20
30
40
50
60
70
80
90 100
PID Reference (%)
4-20mA
Input
4
8
12
16
20
24