Kinetix 5700 System Mounting Toolkit
About the System Mounting Toolkit
The Kinetix® 5700 system mounting toolkit is used to locate the drill-holes for your Kinetix 5700 drive system. Properly spaced drill-holes are
essential for engaging the zero-stack tab and cutout from module-to-module so that the DC-bus connectors are spaced properly to accept the DC-
bus links. The Kinetix 5700 system mounting toolkit can be used with modules with different widths and instructions to do so are included in this
document. The Kinetix 5700 system mounting toolkit includes a drill-hole guide and a mounting bar. Two M4 thread-forming fasteners are also
included.
This document describes how to attach the mounting bar and use the Kinetix 5700 drill-hole guide with different sized modules.
See the Kinetix 5700 Servo Drives User Manual, publication
, for detailed information on wiring, applying power, troubleshooting,
and integration with Logix 5000™ controllers.
Parts List
The Kinetix 5700 mounting toolkit includes:
• Mounting bar
• Drill hole guide
• Two M4 thread-forming fasteners for attaching mounting bar
Required Tools and Components
These tools are required:
• Pencil or other device to draw lines and mark places to drill holes
• Phillips screwdriver
Install the Mounting Bar and Position the Drill-hole Guide
The mounting bar must be mounted horizontally on the system panel. The drill-hole guide inserts behind the mounting bar and slides left and right.
Holes and slots in the drill-hole guide let you establish the location of each Kinetix 5700 drive module. The following instructions are for 55 mm, 85
mm, and 100 mm wide modules. For instructions on how to use the drill-hole guide to map drill-holes for 165 mm, 220 mm, 275 mm, and 440 mm
wide modules, refer to those sections in this document.
Figure 1 - Mounting Bar
Follow these steps to locate the drill-holes for your Kinetix 5700 drive system.
1. Draw a horizontal line on the panel where you would like to position the upper module-width holes (refer to
).
IMPORTANT
In this document hole spacing is measured in millimeters and not converted to inches to avoid errors due to rounding.
2x 190
2x 10
400
3x Ø4.50
10
43.2 Ref
100
100
Drill-hole guide
Mounting Bar
M4 thread-forming
fasteners, 1.7 N•m (15 lb-in)
Dimensions are in millimeters.