Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
165
Troubleshooting the Kinetix 6000 Drive System
Chapter
7
Shunt Module Status Indicators
Each of the shunt module status indicators provide specific troubleshooting
information.
Table 88 - General Shunt Module Troubleshooting
Module
Status
Under These Conditions
Shunt
Fault is latched.
Until fault condition is corrected and cleared.
Fault is cleared.
•
Using MASR, MAFR, MGSR instructions or the HIM (red stop
button).
•
Only after the DC bus is discharged (bus status indicator is
flashing).
•
Drive must be configured with 2094-BSP2 shunt module or Bulletin
1394 external shunt module.
IAM/AM
Disabled (for DC bus
regulation).
•
When the 2094-BSP2 shunt module is used on a 230V system.
•
When either 230V or 460V system is configured with a Bulletin
1394 external shunt module.
•
When configured in Common-bus Follower mode.
Enabled to discharge the
DC bus.
Drive (IAM or leader IAM module) three-phase power is removed.
Disabled from discharging
the DC bus.
When configured in Common-bus Follower mode.
IMPORTANT
Under some fault conditions, two reset commands may be required to
clear drive and shunt module faults.
Содержание Allen-Bradley 2094-BC01-M01-S
Страница 4: ...4 Rockwell Automation Publication 2094 UM001D EN P May 2010 Summary of Changes Notes...
Страница 10: ...10 Rockwell Automation Publication 2094 UM001D EN P May 2010 Table of Contents Notes...
Страница 126: ...126 Rockwell Automation Publication 2094 UM001D EN P May 2010 Chapter 5 Connecting the Kinetix 6000 Drive System Notes...
Страница 228: ...228 Rockwell Automation Publication 2094 UM001D EN P May 2010 Appendix B Interconnect Diagrams Notes...
Страница 270: ...270 Rockwell Automation Publication 2094 UM001D EN P May 2010 Appendix F RBM Module Interconnect Diagrams Notes...
Страница 278: ...278 Rockwell Automation Publication 2094 UM001D EN P May 2010 Index Notes...
Страница 279: ......