Publication 1769-UM002B-EN-P - July 2005
2-12
Installation and Wiring
Effect of Transducer/Sensor and Cable Length Impedance on Voltage Input
Accuracy
For voltage inputs, the length of the cable used between the transducer/sensor
and the 1769-IF4 or -IF8 module can affect the accuracy of the data provided
by the module.
Figure 2.6 Voltage Input Accuracy
Where:
Rc = DC resistance of the cable (each conductor) depending on
cable length
Rs = Source impedance of analog transducer/sensor input
Ri = Impedance of the voltage input
(220 K
Ω
for 1769-IF4 and -IF8)
Vs = Voltage source
(voltage at the transducer/sensor input device)
Vin = Measured potential at the module input
%Ai = Percent added inaccuracy in a voltage-based system due
to source and cable impedance.
For example, for Belden 8761 two conductor, shielded cable:
Rc = 16
Ω
/1000 ft
Rs = 0 (ideal
source)
V in
Vs
Ri
Rc
Rc
Rs
+
-
Vin
Ri
Vs
×
[
]
Rs
2
Rc
×
(
)
Ri
+
+
[
]
-------------------------------------------------------
=
%
Ai
1
Vin
Vs
---------
∠
⎝
⎠
⎛
⎞
100
×
=
Содержание Allen-Bradley 1769-IF4
Страница 1: ...CompactI OAnalog Modules 1769 IF4 IF8 OF2 OF8C and OF8V User Manual ...
Страница 4: ...Publication 1769 UM002B EN P July 2005 Summary of Changes 2 Notes ...
Страница 10: ...Publication 1769 UM002B EN P July 2005 Table of Contents vi ...
Страница 14: ...Publication 1769 UM002B EN P July 2005 4 Notes ...
Страница 118: ...Publication 1769 UM002B EN P July 2005 4 36 Module Data Status and Channel Configuration for the Output Modules Notes ...
Страница 151: ...Publication 1769 UM002B EN P July 2005 Module Addressing and Configuration with MicroLogix 1500 B 9 ...
Страница 152: ...Publication 1769 UM002B EN P July 2005 B 10 Module Addressing and Configuration with MicroLogix 1500 Notes ...
Страница 183: ......