Rockwell Automation Publication 1769-UM012B-EN-P - January 2014
109
Using Electronic Keying
Appendix E
Disabled Keying
Disabled Keying indicates the keying attributes are not considered when
attempting to communicate with a module. Other attributes, such as data size
and format, are considered and must be acceptable before I/O communication is
established. With Disabled Keying, I/O communication may occur with a
module other than the type specified in the I/O Configuration tree with
unpredictable results. We generally do not recommend using Disabled Keying.
EXAMPLE
In the following scenario,
Compatible Keying allows I/O communication
:
The module configuration is for a 1756-IB16D module with module revision
2.1. The physical module is a 1756-IB16D module with module revision 3.2. In
this case, communication is allowed because the major revision of the physical
module is higher than expected and the module determines that it is
compatible with the prior major revision.
IMPORTANT
Changing electronic keying selections online may cause the I/O
communication connection to the module to be disrupted and may result in
a loss of data.
Module Configuration
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IB16D
Major Revision = 2
Minor Revision = 1
Physical Module
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IB16D
Major Revision = 3
Minor Revision = 2
Communication is allowed.
ATTENTION:
Be extremely cautious when using Disabled Keying; if used
incorrectly, this option can lead to personal injury or death, property
damage, or economic loss.
Содержание Allen-Bradley 1769-ASCII
Страница 1: ...Compact I O ASCII Module Catalog Numbers 1769 ASCII User Manual ...
Страница 4: ...4 Rockwell Automation Publication 1769 UM012B EN P January 2014 Summary of Changes Notes ...
Страница 20: ...20 Rockwell Automation Publication 1769 UM012B EN P January 2014 Chapter 1 Compact I O ASCII Module Notes ...
Страница 65: ...Rockwell Automation Publication 1769 UM012B EN P January 2014 65 Configure the 1769 ASCII Module Chapter 2 ...
Страница 67: ...Rockwell Automation Publication 1769 UM012B EN P January 2014 67 Configure the 1769 ASCII Module Chapter 2 ...
Страница 86: ...86 Rockwell Automation Publication 1769 UM012B EN P January 2014 Chapter 3 I O Memory Mapping Notes ...
Страница 96: ...96 Rockwell Automation Publication 1769 UM012B EN P January 2014 Appendix B Status Indicators Notes ...
Страница 101: ...Rockwell Automation Publication 1769 UM012B EN P January 2014 101 Error Codes Appendix C ...
Страница 112: ...112 Rockwell Automation Publication 1769 UM012B EN P January 2014 Appendix E Using Electronic Keying Notes ...
Страница 114: ...114 Rockwell Automation Publication 1769 UM012B EN P January 2014 Appendix F History of Changes Notes ...
Страница 117: ......