CIP services
Chapter 1
Rockwell Automation Publication 1756-PM020F-EN-P - January 2019
21
1st Message Request Field
Bytes (in hex)
Description - Symbolic Segment Addressing
Request Service
4C
Read Tag Service (Request)
Request Path Size
06
Request Path is 6 words (12 bytes) long
Request Path
91 0A 54 6F 74 61 6C 43 6F 75 6E 74
ANSI Ext. Symbolic Segment for
TotalCount
Request Data
01 00
Number of elements to read (1)
1st Message Reply Field
Bytes (in hex)
Description - Symbolic Segment Addressing
Reply Service
CC
Read Tag Service (Reply)
Reserved
00
General Status
00
Success
Extended Status Size
00
No extended status
Reply Data
C4 00
DINT Tag Type Value
16 02 00 00
0000216 = 534 decimal
See also
CIP Services and User-created Tags
Read a single tag named
rate
using
Symbol Instance Addressing. The tag has
a data type of DINT and a value of 534.
1st Message Request Field
Bytes (in hex)
Description - Symbol Instance Addressing
Request Service
4C
Read Tag Service (Request)
Request Path Size
03
Request Path is 3 words (6 bytes) long
Request Path
20 6B
25 00 8F F6
Logical Segment for Symbol Class ID
Logical Segment for Instance ID of the tag
rate
Request Data
01 00
Number of elements to read (1)
1st Message Reply Field
Bytes (in hex)
Description - Symbol Instance Addressing
Reply Service
CC
Read Tag Service (Reply)
Reserved
00
General Status
00
Success
Extended Status Size
00
No extended status
Reply Data
C4 00
DINT Tag Type Value
16 02 00 00
0000216 = 534 decimal
See also
Services Supported by Logix 5000 Controllers
Both Symbolic Segment Addressing and Symbol Instance Addressing may
Example Using Symbol
Instance Addressing
Read Tag Service Error Codes