1
Publication 1747-UM013B-EN-P - January 2005
Appendix
A
Specifications
This appendix provides scanner and system specifications, as well as
throughput information. Topics include:
•
scanner operating specifications
•
network specifications
•
throughput introduction
•
calculating throughput
Scanner Operating
Specifications
Network Specifications
Backplane Current Consumption
600 mA @ 5V dc
Operating Temperature
+32
°
F to 140
°
F (0
°
C to +60
°
C)
Storage Temperature
-40
°
F to 185
°
F (-40
°
C to +85
°
C)
Humidity
5 to 95% without condensation
Noise Immunity
NEMA Standard ICS 2-230
Agency Certification
(when product or packaging is marked)
•
CSA certified
•
CSA Class I, Division 2
Groups A, B, C, D certified
•
UL listed
•
CE marked for all applicable
directives
Table A.1 Baud Rate Determination of Maximum Cable Length and Terminating
Resistor Size
Baud Rate
Maximum Cable
Distance (Belden 9463)
Resistor Size
Using Extended
Node Capability
57.6K baud
3048 meters (10,000 feet)
82 ohm 1/2 Watt
Brown - Green -
Brown - Gold
115.2K baud
1524 meters (5000 feet)
230.4K baud
762 meters (2500 feet)
Not Using Extended
Node Capability
57.6K baud
3048 meters (10,000 feet)
150 ohm 1/2 Watt
Brown - Green -
Brown - Gold
115.2K baud
1524 meters (5000 feet)
230.4K baud
762 meters (2500 feet)
82 ohm 1/2 Watt Gray
- Red - Black - Gold
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com