100
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
Chapter 5
Configure the Module in a GuardLogix Controller System
Values and States of Tags
This table shows the values and states of the tags.
Data
Description
Digital Input Data
Run Mode
STANDARD
Indicates whether consumed data is actively being updated by a device that is in one of these
states:
•
Run mode: 1 Idle State: 0
Connection Faulted
STANDARD
Indicates the validity of the safety connection between the safety producer and the safety
consumer.
•
Valid: 0 Faulted: 1
Safety Input Data
SAFETY
Indicates the ON/OFF state of each input circuit.
•
ON: 1 OFF: 0
Combined Safety Input Status
SAFETY
An AND of the status of all input circuits.
•
All circuits are normal: 1
•
An error was detected in one or more input circuits: 0
Individual Safety Input Status
SAFETY
Indicates the status of each input circuit.
•
Normal: 1 Fault (Alarm): 0
Combined Safety Output Status
SAFETY
An AND of the status of all safety output circuits.
•
All circuits are normal: 1
•
An error has been detected in one or more output circuits: 0
Individual Safety Output Status
SAFETY
Indicates the status of each safety output circuit.
•
Normal: 1 Fault (Alarm): 0
Muting Lamp Status
SAFETY
Indicates the status when circuit T1 and T3 is configured as the muting lamp output.
•
Normal: 1 Fault (Alarm): 0
Output Readback
STANDARD
Monitors the presence of 24V on the output circuit. Readback is ON (1) if 24V is on output
terminal.
•
ON: 1 OFF: 0
Individual Test Output Status
STANDARD
Indicates the status of each of the test output circuits.
•
Normal: 1 Fault (Alarm): 0
Input Power Error Bit
Indicates field power supplied is within specification.
•
Power error: 1 Power OK: 0
Output Power Error Bit
Indicates field power supplied is within specification.
•
Power error: 1 Power OK: 0
Digital Output Data
Safety Output Data
SAFETY
Controls the safety output.
•
ON: 1 OFF: 0
Standard Output Data
STANDARD
Controls the test output when Test Output mode is set to a standard output.
•
ON: 1 OFF: 0
Содержание Allen-Bradley 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Страница 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Страница 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Страница 22: ...22 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 1 POINT Guard I O Overview Notes ...
Страница 150: ...150 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 8 Replacing POINTGuard I O Modules Notes ...
Страница 180: ...180 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix C Specifications Notes ...
Страница 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Страница 190: ...190 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix E Configuration Parameters Notes ...
Страница 204: ...204 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix G History of Changes Notes ...
Страница 211: ......