22
Rockwell Automation Publication 1609-UM009D-EN-P - February 2021
Troubleshooting
Troubleshooting
Button
Function
Explanation
UPS Output Enable
Press and hold the button until one beep is heard, then release
immediately
UPS Output Disable
Press and hold the button until three beeps are heard, then release
immediately
Self-Test
Press and hold the button until two beeps are heard, then release
immediately (The UPS must operate for at least 4 hours before executing
this function)
Problem
Possible Cause
Solution
No LED illuminates /
No alarm
UPS output is disabled or input utility
power is not present
Have qualified electrician trouble shoot the input utility
power system and make the necessary corrections.
No UPS output
The UPS has not been enabled
Manually Enable
- Make sure that the Remote Function
selector switch is in the Disable position, then press and
hold the UPS Power button until one beep is heard and
release immediately.
Remotely Enable
- Make sure that the Remote Function
selector switch is in the Enable position and verify that
there is an adequate connection to the remote on/off dry
I/O connection (terminals 7 & 8)
UPS Operates on battery
although input utility
voltage exists
The system can experience high, low,
or distorted input utility voltage
Reduce the UPS sensitivity by using the 1609 UPS
Management software.
If the problem persists, move or connect the UPS with a
known good quality, utility power source.
Input line utility power
circuit breaker trip
The system can have experienced an
overload
Verify that the circuit breaker is sized properly.
Verify the load that is connected to the output of the UPS.
Ensure that the load does not exceed the output rating of
the UPS.
FAULT LED illuminates
An internal fault has been detected
Refer to the UPS LED Fault Indicators to identify the specific
fault that occurred and possible resolution.
ONLINE LED illuminates, but
no UPS output is available
The UPS output connection cannot be
connected properly
Disable the UPS output and have qualified electrician
troubleshoot the output connection system and make the
necessary corrections.
The battery did not provide
expected runtime
The batteries might be weak or the
lifespan is due
Charge the batteries for 8 hours and retest the runtime.
If the runtime is still less than expected after charging,
replace the batteries even if the Replace Battery LED doesn’t
illuminate.
No communication
between the
UPS and your PC
Wrong cable
Verify cable used.
The connection cable is not firmly
connected
Reconnect the communication cable firmly.
PC Communication Port can have
been used by another process or is
defective
Check if there is other software or service accessing the
Communication Port on your PC, or connect it to a different
communication port.
There is interference on the
connection cable
Lay the cable differently or away from other cables and
reconnect the cable.
Содержание Allen-Bradley 1609-B Series
Страница 1: ...Uninterruptible Power Supplies Bulletin Numbers 1609 B and 1609 D User Manual Original Instructions...
Страница 4: ...4 Rockwell Automation Publication 1609 UM009D EN P February 2021 Preface Notes...
Страница 6: ...6 Rockwell Automation Publication 1609 UM009D EN P February 2021 Table of Contents Notes...