Power Supply —12V, 10 A, 120 W, Single Phase
Electromagnetic
Compatibility
The electromagnetic compatibility (EMC) behavior of the device is designed
for applications in industrial, residential, commercial, and light industry
environments.
The device is investigated according to EN 61000-6-1, EN 61000-6-2,
EN 61000-6-3 and EN 61000-6-4.
EMC Immunity
Electrostatic
discharge
EN 61000-4-2
Contact discharge Air discharge
8 kV 15 kV
Criterion A
(1)
Criterion A
(1)
Performance Criteria:
A: The device shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. The device may shut-down and restarts by itself. No damage or hazards for the
device will occur.
Electromagnetic RF EN 61000-4-3
80 MHz…2.7 GHz
20V/m
Criterion A
Fast transients
(Burst)
EN 61000-4-4
Input lines Output lines
DC OK signal (coupling clamp)
4 kV
2 kV
2 kV
Criterion A
Criterion A
Criterion A
Surge voltage on
input
EN 61000-4-5
L
N
L
PE, N
PE
4 kV
2 kV
Criterion A
Criterion A
Surge voltage on
output
EN 61000-4-5
+
-
+ / -
PE
1 kV
2 kV
Criterion A
Criterion A
Surge voltage on
EN 61000-4-5
DC OK signal
PE
1 kV
Criterion A
Conducted EN
61000-4-6
0.15…80
MHz
20V
Criterion
A
Mains voltage dips
EN 61000-4-11
0% of 100V AC
40% of 100V AC
70% of 100V AC
0% of 200V AC
40% of 200V AC
40% of 200V AC
70% of 200V AC
0V AC, 20 ms
40V AC, 200 ms
70V AC, 500 ms
0V AC, 20 ms
80V AC, 200 ms <8 A
80V AC, 200 ms >8 A
140V AC, 500 ms
Criterion A
Criterion C
Criterion A
Criterion A
Criterion A
Criterion C
Criterion A
Voltage
EN 61000-4-11
0% of 200V AC (=0V)
5000 ms
Criterion C
Powerful transients VDE 0160
Over entire load range
750V, 0.3 ms
Criterion A
EMC Emission
Conducted emission input lines
EN 55011, EN 55022, FCC Part 15,
CISPR 11, CISPR 22
Class B
Conducted emission output
lines
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
Limits for local DC power networks fulfilled
Radiated emission
EN 55011, EN 55022
Class B
Harmonic input current (PFC)
EN 61000-3-2
Fulfilled for Class A equipment
Voltage fluctuations, flicker
EN 61000-3-3
Fulfilled, tested with constant current loads,
non pulsing
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Switching Frequencies
PFC converter
30 kHz…140 kHz
Input voltage and output power dependent
Main converter
60 kHz…140 kHz
Output load dependent
Auxiliary converter
30 kHz…60 kHz
Output load dependent