![Rockwell Automation Allen-Bradley 1606-XLB120E Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/rockwell-automation/allen-bradley-1606-xlb120e/allen-bradley-1606-xlb120e_reference-manual_1475736023.webp)
Rockwell Automation Publication 1606-RM055B-EN-P - February 2017
23
Basic Power Supply 5 A
Approximate Dimensions
and Weight
Dimensions are in mm (in).
Figure 25 - Front View
Figure 26 - Side View
Attribute
1606-XLB120E
Width
39 mm (1.54 in.)
Height
125 mm (4.92 in.)
Depth
(1)
(1) The DIN rail height must be added to the unit depth to calculate the total required installation depth.
128.95 mm (5.08 in.)
Weight
370 g (0.81 lb)
DIN Rail
Use 35 mm DIN rails according to EN 60715 or EN 50022 with a height of 7.5 or 15 mm.
Plastic Material of Housing
Flame retardant Polycarbonate (PC) - UL94-V0 Vicat softening temperature specified
with 149 °C according to ASTM D1525
Installation Clearances
Keep the following installation clearances: 40 mm on top, 20 mm on the bottom, 5
mm on the left and right sides are recommended when the device is loaded
permanently with more than 50% of the rated power. Increase this clearance to 15 mm
in case the adjacent device is a heat source (for example, another power supply).
39
(1.54)
125
(4.92)
128.95
(5.08)