Chapter
6
Troubleshooting
Fault Information
This chapter provides information to guide you in troubleshooting the drive.
Included is a list and description of drive faults and problems that may occur.
Program Keypad Module Fault Display
Figure 6.1
Ready/Fault Indicating Panel
Figure 6.2
How to Clear a Fault
When a fault occurs, the cause must be corrected before the fault can be cleared.
After corrective action has been taken, any of the following actions will clear the
fault.
• Press the Program Keypad Module’s Stop button.
• Disconnect power to the drive, wait one minute, reapply power.
• Cycle the input signal at TB3-8 to the drive.
• Set
P54 - [Clear Fault]
to 1.
Active Fault
If a fault occurs,
P07 - [Active Fault]
is displayed.
Fault Code Number
Controllers equipped with a
Program Keypad Module will flash
the display when a fault is present.
FAULT
READY
Fault LED
Controllers without a Program
Keypad Module come equipped
with a Ready/Fault Indicating Panel.
When the Fault LED is illuminated,
a fault exists. The optional Remote
Programming Adapter is equipped
with the same Ready/Fault indication
system.