Rockwell Automation Publication 150-UM009E-EN-P - August 2021
20
Chapter
3
Programming
DIP Switch Settings
Program the 150-E elevator controller with the DIP switches that are located on
the front of the controller. The DIP switch settings define all functionality. The
following tables define the settings available within the SMC™ controller. The
default settings are shaded.
Table 7 - Start Time
Setting [seconds]
Switch #1
Switch #2 Description
2
OFF
OFF
This defines the time for which the controller ramps or limits
current to the motor. The controller can determine when the
motor is up-to-speed (UTS), it may transition to bypass before
this time expires. If the motor does not reach speed before the
time expires, the controller continues under SCR control and
does not close the bypass contactor.
5
ON
OFF
10
OFF
ON
15
ON
ON
Table 8 - Start Mode
Mode Setting
Switch #3
Description
Current Limit
OFF
In Current Limit mode, a set level of current is applied to the motor over the
start time. In Soft Start mode, the device ramps the torque from the initial
level to 100% over the start time.
Soft Start
ON
Table 9 - Current Limit/Initial Torque Level
% FLA/ % Torque
Switch #4
Switch #5 Description
150%/15%
OFF
OFF
The level indicated by this programming applies an initial level
of current or torque to the motor for the start time. For
example, if switch #3 is set to OFF, the device performs a
current limit start at the level indicated by these switches.
250%/25%
ON
OFF
350%/35%
OFF
ON
450%/65%
ON
ON
Table 10 - Soft Stop Time
Settings [seconds]
Switch #6
Switch #7 Description
OFF
OFF
OFF
Soft Stop reduces the voltage that is applied to the motor
over the programmed period of time. The soft stop is
complete when the soft stop timer has expired or the
current measured drops below 50% of the FLA setting.
1 x start time
ON
OFF
2 x start time
OFF
ON
3 x start time
ON
ON
Table 11 - Phase Rotation
Setting
Switch #9 Description
ABC rotation
OFF
This switch defines the allowable phase rotation of the motor.
CBA rotation
ON
Table 12 - Phase Imbalance
Setting
Switch #10 Description
Enabled
OFF
The controller can monitor for imbalance between phase currents. You can
disable this protection feature.
Disabled
ON