A-2
Motor Cable Length Restrictions Tables
TIP:
To increase the distance between the drive and the motor, some device (RWR or
Terminator) needs to be added to the system
Table A.A
1336 PLUS II/IMPACT Drive, 380-480V in met
ers (feet)
➊
Drive
Frame
Drive kW
(hp)
Motor
kW (hp)
No External Devices
w/1204-TFB2 Term. w/1204-TFA1 Terminator
Reactor
at
Drive
➋
Motor Motor
Motor
Motor
A
B
1329 1329R/L (1850V) A or B
1329
A
B
1329 A
B or
1329
Any
Cable
Any
Cable
Any
Cable
Any
Cable
➏
Cable Type
Any
Cable
Cable Type
Cable Type
Any
Cable
Any
Cable
Any
Cable
Shld
.
➌
Unshld.
Shld.
➌
Unshld.
Shld.
➌
Unshld.
A1
0.37 (0.5)
0.37 (0.5) 12.2
(40)
33.5
(110)
91.4
(300)
91.4
(300)
30.5
(100)
61.0
(200)
30.5
(100)
61.0
(200)
91.4
(300)
22.9
(75)
182.9
(600)
0.75 (1)
0.75 (1)
12.2
(40)
33.5
(110)
91.4
(300)
91.4
(300)
30.5
(100)
30.5
(100)
30.5
(100)
30.5
(100)
91.4
(300)
22.9
(75)
182.9
(600)
0.37 (0.5) 12.2
(40)
33.5
(110)
91.4
(300)
91.4
(300)
Use 1204-TFA1
30.5
(100)
61.0
(200)
30.5
(100)
61.0
(200)
91.4
(300)
22.9
(75)
182.9
(600)
1.2 (1.5)
1.2 (1.5)
12.2
(40)
33.5
(110)
91.4
(300)
91.4
(300)
30.5
(100)
30.5
(100)
61.0
(200)
61.0
(200)
91.4
(300)
22.9
(75)
182.9
(600)
0.75 (1)
12.2
(40)
33.5
(110)
91.4
(300)
91.4
(300)
30.5
(100)
30.5
(100)
61.0
(200)
61.0
(200)
91.4
(300)
22.9
(75)
182.9
(600)
0.37 (0.5) 12.2
(40)
33.5
(110)
114.3
(375)
121.9
(400)
30.5
(100)
30.5
(100)
61.0
(200)
61.0
(200)
121.9
(400)
22.9
(75)
182.9
(600)
A2
1.5 (2)
1.5 (2)
7.6
(25)
12.2
(40)
91.4
(300)
91.4
(300)
91.4
(300)
91.4
(300)
91.4
(300)
30.5
(100)
30.5
(100)
91.4
(300)
61.0
(200)
91.4
(300)
22.9
(75)
182.9
(600)
1.2 (1.5)
7.6
(25)
12.2
(40)
114.3
(375)
182.9
(600)
91.4
(300)
182.9
(600)
182.9
(600)
30.5
(100)
30.5
(100)
91.4
(300)
61.0
(200)
182.9
(600)
22.9
(75)
182.9
(600)
0.75 (1)
7.6
(25)
12.2
(40)
114.3
(375)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
30.5
(100)
30.5
(100)
91.4
(300)
61.0
(200)
182.9
(600)
22.9
(75)
182.9
(600)
0.37 (0.5) 7.6
(25)
12.2
(40)
114.3
(375)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
30.5
(100)
30.5
(100)
91.4
(300)
61.0
(200)
182.9
(600)
22.9
(75)
182.9
(600)
2.2 (3)
2.2 (3)
7.6
(25)
12.2
(40)
91.4
(300)
91.4
(300)
182.9
(600)
182.9
(600)
182.9
(600)
Use 1204-TFB2
22.9
(75)
182.9
(600)
1.5 (2)
7.6
(25)
12.2
(40)
114.3
(375)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
22.9
(75)
182.9
(600)
0.75 (1)
7.6
(25)
12.2
(40)
114.3
(375)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
22.9
(75)
182.9
(600)
0.37 (0.5) 7.6
(25)
12.2
(40)
114.3
(375)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
22.9
(75)
182.9
(600)
A3
3.7 (5)
3.7 (5)
7.6
(25)
12.2
(40)
114.3
(375)
Note
For applications/
installations using
new motors, no
restrictions in lead
length due to volt-
age reflection are
necessary. You
should observe
standard practices
for voltage drop,
cable capacitance,
and other issues.
For retrofit situa-
tions, check with
the motor manufac-
turer for insulation
rating.
182.9
(600)
182.9
(600)
182.9
(600)
22.9
(75)
182.9
(600)
2.2 (3)
7.6
(25)
12.2
(40)
114.3
(375)
182.9
(600)
182.9
(600)
182.9
(600)
22.9
(75)
182.9
(600)
1.5 (2)
7.6
(25)
12.2
(40)
114.3
(375)
182.9
(600)
182.9
(600)
182.9
(600)
22.9
(75)
182.9
(600)
0.75 (1)
7.6
(25)
12.2
(40)
114.3
(375)
182.9
(600)
182.9
(600)
182.9
(600)
22.9
(75)
182.9
(600)
0.37 (0.5) 7.6
(25)
12.2
(40)
114.3
(375)
182.9
(600)
182.9
(600)
182.9
(600)
22.9
(75)
182.9
(600)
A4
5.5-15
(7.5-20)
5.5-15
(7.5-20)
7.6
(25)
12.2
(40)
114.3
(375)
182.9
(600)
182.9
(600)
182.9
(600)
24.4
(80)
182.9
(600)
B
11-22
(15-30)
11-22
(15-30)
7.6
(25)
12.2
(40)
114.3
(375)
182.9
(600)
182.9
(600)
182.9
(600)
24.4
(80)
182.9
(600)
C
30-45
(X40-X60)
30-45
(40-60)
7.6
(25)
12.2
(40)
114.3
(375)
182.9
(600)
182.9
(600)
182.9
(600)
76.2
(250)
182.9
(600)
D
45-112
(60-X150)
45-112
(60-150)
12.2
(40)
30.5
(100)
114.3
(375)
182.9
(600)
182.9
(600)
182.9
(600)
61.0
(200)
91.4
(300)
E
112-187
(150-250)
112-187
(150-250)
12.2
(40)
53.3
(175)
114.3
(375)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
F
187-336
(250-450)
187-336
(250-450)
18.3
(60)
53.3
(175)
114.3
(375)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
G
187-448
(X250-600)
187-448
(250-600)
18.3
(60)
53.3
(175)
114.3
(375)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
Содержание Allen-Bradley 1305-AA02A
Страница 1: ...Installation Instructions Wiring and Grounding Guidelines for Pulse Width Modulated PWM AC Drives ...
Страница 4: ...ii Summary of Changes Notes ...
Страница 40: ...2 18 Power Distribution Notes ...
Страница 48: ...3 8 Grounding Notes ...
Страница 68: ...4 20 Practices Notes ...
Страница 78: ...6 8 Electromagnetic Interference Notes ...
Страница 94: ...Glossary 4 UL Underwriters Laboratories ...
Страница 100: ...Index 6 ...
Страница 101: ......