Chapter 6 Micro870 Controller Distributed Network Protocol
Local Port Number (TCP)
This value is used to configure Local TCP Port Number which is used for TCP socket listening.
The valid range is 0…65535. Default value is 20000.
DNP3 Slave Application Layer Configuration Parameters
Channel for Unsolicited Response
Only channels already configured for DNP3 protocol appear in the Channel for Unsolicited
Response dropdown menu. Any and all Unsolicited Responses are transmitted via this selected
channel.
Restore Events After Power Cycle
When the selection is Disabled (Unchecked), DNP3 events which are generated before a power
cycle are flushed after a power cycle. When the option is Enabled (Checked), all DNP3 events
are restored after a power cycle.
Valid selections are Enabled (Checked) and Disabled (Unchecked), with disabled as default
value.
Unsolicited Responses On Start Up
Valid selections are Enabled (Checked) and Disabled (Unchecked). Default value is Disabled
(Unchecked).
When the selection is Disabled (Unchecked), the controller does not send any enabled
Unsolicited Responses after a restart until it has received a FC_ENABLE_UNSOLICITED (20)
command from the DNP3 Master.
When the selection is Enabled (Checked), the controller sends any enabled Unsolicited
Responses after a restart to the DNP3 Master unconditionally.
Unsolicited Responses For Class1
Valid selections are Enabled (Checked) and Disabled (Unchecked). Default value is Disabled
(Unchecked).
When the selection is Disabled (Unchecked), Unsolicited Response is disabled for Class 1
events. To prevent overflowing of the event buffer, DNP3 Master should poll for Class 1 events.
When the selection is Enabled (Checked), Unsolicited Response is enabled for Class 1 events.
Содержание 2080-L50E-24AWB
Страница 14: ...14 Rockwell Automation Publication 2080 UM002N EN E November 2022 Notes ...
Страница 54: ...54 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 4 Wire Your Controller Notes ...
Страница 128: ...128 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 7 Program Execution in Micro800 Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 8 EtherNet IP Network Notes ...
Страница 198: ...198 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 9 Motion Control Notes ...
Страница 232: ...232 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 11 Controller Security Notes ...
Страница 260: ...260 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 12 Using microSD Cards Notes ...
Страница 266: ...266 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix A Modbus Mapping for Micro800 Notes ...
Страница 275: ...Rockwell Automation Publication 2080 UM002N EN E November 2022 275 Appendix B Quickstarts 10 Click Finish to complete ...
Страница 332: ...332 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix E PID Function Blocks Notes ...
Страница 352: ...352 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix G Connect to Networks using DF1 Notes ...
Страница 388: ...388 Rockwell Automation Publication 2080 UM002N EN E November 2022 Index Notes ...