Rockwell Automation Publication 2080-UM002N-EN-E - November 2022
299
Appendix C User Interrupts
The STIS instruction can be used to start and stop the STI function or to change the time
interval between STI user interrupts. The STI instruction has two operands:
•
IRQType
— This is the STI ID that a user wants to drive.
•
SetPoint
— This is the amount of time (in milliseconds) which must expire prior to
executing the selectable timed user interrupt. A value of zero disables the STI function.
The time range is from 0…65,535 milliseconds.
The STIS instruction applies the specified set point to the STI function as follows (STI0 is used
here as an example):
• If a zero set point is specified, the STI is disabled and STI0.Enable is cleared (0).
• If the STI is disabled (not timing) and a value greater than 0 is entered into the set point,
the STI starts timing to the new set point and STI0.Enable is set (1).
• If the STI is currently timing and the set point is changed, the new setting takes effect
immediately, restarting from zero. The STI continues to time until it reaches the new set
point.
UID - User Interrupt Disable
The UID instruction is used to disable selected user interrupts. The table below shows the
types of interrupts with their corresponding disable bits:
Table 73 - Types of Interrupts Disabled by the UID Instruction
Interrupt Type
Element
Decimal Value
Corresponding Bit
Plug-In Module
UPM4
8388608
bit 23
Plug-In Module
UPM3
4194304
bit 22
Plug-In Module
UPM2
2097152
bit 21
Plug-In Module
UPM1
1048576
bit 20
Plug-In Module
UPM0
524288
bit 19
STI - Selectable Timed Interrupt
STI3
262144
bit 18
STI - Selectable Timed Interrupt
STI2
131072
bit 17
STI - Selectable Timed Interrupt
STI1
65536
bit 16
STI - Selectable Timed Interrupt
STI0
32768
bit 15
EII - Event Input Interrupt
Event 7
16384
bit 14
EII - Event Input Interrupt
Event 6
8192
bit 13
EII - Event Input Interrupt
Event 5
4096
bit 12
EII - Event Input Interrupt
Event 4
2048
bit 11
HSC - High-Speed Counter
HSC5
1024
bit 10
HSC - High-Speed Counter
HSC4
512
bit 9
HSC - High-Speed Counter
HSC3
256
bit 8
HSC - High-Speed Counter
HSC2
128
bit 7
HSC - High-Speed Counter
HSC1
64
bit 6
HSC - High-Speed Counter
HSC0
32
bit 5
EII - Event Input Interrupt
Event 3
16
bit 4
EII - Event Input Interrupt
Event 2
8
bit 3
EII - Event Input Interrupt
Event 1
4
bit 2
EII - Event Input Interrupt
Event 0
2
bit 1
UFR - User Fault Routine Interrupt
UFR
1
bit 0 (reserved)
UID
UID
UID (name or Pin ID)
or ENO(Pin ID)
Enable
IRQType
Содержание 2080-L50E-24AWB
Страница 14: ...14 Rockwell Automation Publication 2080 UM002N EN E November 2022 Notes ...
Страница 54: ...54 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 4 Wire Your Controller Notes ...
Страница 128: ...128 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 7 Program Execution in Micro800 Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 8 EtherNet IP Network Notes ...
Страница 198: ...198 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 9 Motion Control Notes ...
Страница 232: ...232 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 11 Controller Security Notes ...
Страница 260: ...260 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 12 Using microSD Cards Notes ...
Страница 266: ...266 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix A Modbus Mapping for Micro800 Notes ...
Страница 275: ...Rockwell Automation Publication 2080 UM002N EN E November 2022 275 Appendix B Quickstarts 10 Click Finish to complete ...
Страница 332: ...332 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix E PID Function Blocks Notes ...
Страница 352: ...352 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix G Connect to Networks using DF1 Notes ...
Страница 388: ...388 Rockwell Automation Publication 2080 UM002N EN E November 2022 Index Notes ...