
Rockwell Automation Publication 2080-UM002N-EN-E - November 2022
185
Chapter 9 Motion Control
Table 32 - Dynamics Parameters
Parameter
Values
Start/Stop Velocity
(1)
(2)
(1) The parameter is set as REAL (float) value in Connected Components Workbench. To learn more about conversions and
rounding of REAL values, see
Real Data Resolution on page 187
(2) The formula for deriving rpm to user unit, and vice versa:
The range is based on Motor and Load parameters (See
Range
1…100,000 pulse/sec
Default
: 300 rpm
For example, you can configure the value from 0.005…500 mm/s for 200 pulses
per revolution and units of 1 mm per revolution.
(3)
Rpm value is automatically populated when a value in user units is specified, but
the user can also initially enter an rpm value.
Start/stop velocity should not be greater than maximum velocity.
(3) To convert from parameter value from pulse to user units:
Start/Stop Velocity in rpm
(1) (2)
Max Velocity
(1) (2)
The range is based on Motor and Load parameters (See
Range: 1…10,000,000 pulse/sec.
Default: 100,000.0 pulse/sec
Max Acceleration
(1)
The range is based on Motor and Load parameters (See
Range
: 1…10,000,000 pulse/sec
2
Default
: 10,000,000 pulse/sec
2
Max Deceleration
(1)
The range is based on Motor and Load parameters (See
Range
: 1…100,000 pulse/sec
2
Default
: 10,000,000 pulse/sec
2
Max Jerk
(1)
The range is based on Motor and Load parameters (See
Range
: 0…10,000,000 pulse/sec
3
Default
: 10,000,000 pulse/sec
3
Emergency Stop Profile
Defines stop type, velocity, deceleration, and jerk values.
Stop Type
Set as Deceleration Stop (default) or Immediate Stop.
Stop Velocity
(1)
The range is based on Motor and Load parameters (See
Range
: 1…100,000 pulse/sec
Default
: 300 rpm
Stop Deceleration
(1)
The range is based on Motor and Load parameters (See
Range
: 1…10,000,000 pulse/sec
Default
: 300.0 rpm
2
Stop Jerk
(1)
The range is based on Motor and Load parameters (See
Range
: 0...10,000,000 pulse/sec
3
Default
: 0.0 rpm
3
(Disabled)
A red border on an input field indicates that an invalid value has been
entered. Scroll over the field to see tooltip message that will let you
know the valid value range for the parameter. Supply the valid value.
v (in rpm) = v (in user unit/sec) x 60 s
travel per revolution (in user unit)
Travel per revolution
Pulse per revolution
Value in user unit = Value in pulse x
Содержание 2080-L50E-24AWB
Страница 14: ...14 Rockwell Automation Publication 2080 UM002N EN E November 2022 Notes ...
Страница 54: ...54 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 4 Wire Your Controller Notes ...
Страница 128: ...128 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 7 Program Execution in Micro800 Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 8 EtherNet IP Network Notes ...
Страница 198: ...198 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 9 Motion Control Notes ...
Страница 232: ...232 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 11 Controller Security Notes ...
Страница 260: ...260 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 12 Using microSD Cards Notes ...
Страница 266: ...266 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix A Modbus Mapping for Micro800 Notes ...
Страница 275: ...Rockwell Automation Publication 2080 UM002N EN E November 2022 275 Appendix B Quickstarts 10 Click Finish to complete ...
Страница 332: ...332 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix E PID Function Blocks Notes ...
Страница 352: ...352 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix G Connect to Networks using DF1 Notes ...
Страница 388: ...388 Rockwell Automation Publication 2080 UM002N EN E November 2022 Index Notes ...