Appendix F MicroLogix 1400 Distributed Network Protocol
These control codes and point models are implemented in the controller:
•
0x00 (NUL/NUL): Clear field Off
•
0x20 (NUL/NUL): Clear field On
•
0x01 (Pulse On/NUL): Clear field Off, Activation Model
•
0x21 (Pulse On/NUL): Clear field On, Activation Model
•
0x03 (Latch On/NUL): Clear field Off, Complementary latch model
•
0x23 (Latch On/NUL): Clear field On, Complementary latch model
•
0x04 (Latch Off/NUL): Clear field Off, Complementary latch model
•
0x24 (Latch Off/NUL): Clear field On, Complementary latch model
•
0x41 (Pulse On/Close): Clear field Off, Complementary two-output model
•
0x61 (Pulse On/Close): Clear field On, Complementary two-output model
•
0x81 (Pulse On/Trip): Clear field Off, Complementary two-output model
•
0xA1 (Pulse On/Trip): Clear field On, Complementary two-output model
When the controller is in Non-executing mode, the controller will not accept a
Binary Command. The controller returns a Control Status Code 7 in response.
To access objects 12(CROB), the controller should be in Executing mode.
Note that Executing mode includes Run, Remote Run, Test Continuous Scan,
and Test Single Scan modes. Any others are Non-executing modes.
DNP3 Double Bit Binary Input Object
The supported object group and variations are listed in this section. The
controller responds with the default group and variation when the DNP3
Master requests to read an object with Any variation.
Double-bit Binary Input Static Objects:
•
g3v0 – Double-bit Binary Input – All Variations
•
g3v1 – Double-bit Binary Input – Packed format (default)
•
g3v2 – Double-bit Binary Input – With flags
Double-bit Binary Input Event Objects:
•
g4v0 – Double-bit Binary Input Event – All Variations
•
g4v1 – Double-bit Binary Input Event – Without time
•
g4v2 – Double-bit Binary Input Event – With absolute time
•
g4v3 – Double-bit Binary Input Event – With relative time (default)
Related Object File Number:
•
Double Bit Binary Input Object File Number
Table 27 - Point Index
Binary Output Database Index
Activation Model or Complementary Latch Model
Complementary Two-output Model
0
BO Index 0
BO Close Index 0
1
BO Index 1
BO Trip Index 0
2
BO Index 2
BO Close Index 1
3
BO Index 3
BO Trip Index 1
4
BO Index 4
BO Close Index 2
5
BO Index 5
BO Trip Index 2
…
…
…
4094
BO Index 4094
BO Close Index 2047
4095
BO Index 4095
BO Trip Index 2047
Содержание 1766-L32AWA
Страница 10: ...10 Rockwell Automation Publication 1766 UM001O EN P September 2021 Table of Contents Notes ...
Страница 18: ...18 Rockwell Automation Publication 1766 UM001O EN P September 2021 Chapter 1 Hardware Overview Notes ...
Страница 56: ...56 Rockwell Automation Publication 1766 UM001O EN P September 2021 Chapter 3 Wire Your Controller Notes ...
Страница 122: ...122 Rockwell Automation Publication 1766 UM001O EN P September 2021 Chapter 5 LCD and Keypad Notes ...
Страница 152: ...152 Rockwell Automation Publication 1766 UM001O EN P September 2021 Appendix B Replacement Parts Notes ...
Страница 160: ...160 Rockwell Automation Publication 1766 UM001O EN P September 2021 Appendix C Troubleshoot Your System Notes ...
Страница 302: ...302 Rockwell Automation Publication 1766 UM001O EN P September 2021 Glossary Notes ...
Страница 308: ...308 Rockwell Automation Publication 1766 UM001O EN P September 2021 Index Notes ...