Rockwell Automation Publication 1756-IN048D-EN-P - March 2021
GuardLogix 5580 Controllers Installation Instructions
Specifications
European Machinery Directive Approval
The following applies to products with EU Machinery Directive certification:
•
Are in conformity with the essential requirements of the EU Machinery Directive (2006/42/EC) when installed in accordance with the instructions contained in the
product documentation.
•
The type of protection is Cat. 4/PL e according to EN ISO 13849-1 and SIL CL 3 according to EN/IEC 62061 when used in combination with the 1756-L8SP safety
partner.
•
The type of protection is Cat. 3/PL d according to EN ISO 13849-1, and SIL CL 2 according to EN/IEC 62061 when not used in combination with the 1756-L8SP safety
partner.
•
Comply to Standards EN ISO 13849-1:2015 and EN62061:2005 + A1:2013 + A2:2015, reference EC-Type certificate number TÜV 01/205/5611.
•
See the Product Certification link at
or Declarations of Conformity, Certificates, and other certification details including a full list of
safety-related certifications.
•
May have catalog numbers followed by a ‘K’ to indicate a conformal coating option.
Attribute
1756-L81ES, 1756-L81ESK, 1756-L82ES, 1756-L82ESK, 1756-L83ES, 1756-L83ESK, 1756-L84ES, 1756-L84ESK,
1756-L8SP, 1756-L8SPK
Temperature, operating (SIL 2/PLd)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F) for Series C Chassis
Note: If operating above +55 °C (+131 °F), modules greater than 6.2W shall not be installed in slots adjacent to the
controller.
Temperature, operating (SIL 3/PLe)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F) for Series C Chassis
0 °C < Ta < +50 °C (+32 °F < Ta < +122 °F) for Series B Chassis
Temperature, Surrounding Air, max (SIL 2/PLd)
60 °C (140 °F) for Series C Chassis
Note: If operating above +55 °C (+131 °F), modules greater than 6.2W shall not be installed in slots adjacent to the
controller.
Temperature, Surrounding Air, max (SIL 3/PLe)
60 °C (140 °F) for Series C Chassis
50 °C (122 °F) for Series B Chassis
Enclosure type rating
None (open-style)
Corrosive Atmosphere
(1)
• ASTM B845-97 Method H Accelerated Test
(20-Day Exposure)
(1) Only applicable to modules that end with a ‘K’.
Severity Level G3
(2)
per ANSI/ISA 71.04–2013, Airborne Contaminants—Gases
Severity Level CX
(2)(3)
per IEC 60721-3-3:2019, Chemically Active Substances
(2) Port Plugs must remain installed in unused ports at all times during storage and operation for the product to meet it’s corrosive atmosphere rating.
(3) Up to 9.6 microns per year, corrosion rate of copper.
Voltage and current ratings
1.20 A @ 5.1V DC
5.0 mA @ 1.2V DC
Isolation Voltage
50V (continuous), Basic Insulation Type, Ethernet to Backplane, USB to Backplane, and USB to Ethernet
Type tested at 1000V AC for 60 seconds
Weight, approx
394 g (0.868 lb)
Wire size
Ethernet connections:
Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2.
North American Temp Code
T4
ATEX Temp Code
T4
IECEx Temp Code
T4