Rockwell Automation Publication 1756-IN048D-EN-P - March 2021
3
GuardLogix 5580 Controllers Installation Instructions
Product Advisories
ATTENTION:
• In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for repair.
Do not dismantle the module.
• The USB port is intended for temporary local programming purposes only and not intended for permanent connection. The USB cable
is not to exceed 3.0 m (9.84 ft) and must not contain hubs.
• Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.
• When installed in a 1756 Series C Chassis, this equipment is certified for use only within the surrounding air temperature range
of 0…60 °C (32…140 °F). The equipment must not be used outside of this range.
• When installed in a 1756 Series B Chassis, this equipment is certified for use only within the surrounding air temperature range
of 0…50 °C (32…122 °F). The equipment must not be used outside of this range.
WARNING:
• When you press the reset button while power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be
sure that power is removed or the area is nonhazardous before proceeding.
• Do not use the USB port in hazardous locations.
North American Hazardous Location Approval
The following information applies when operating this equipment in
hazardous locations.
Informations sur l’utilisation de cet équipement en environnements dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division
2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each
product is supplied with markings on the rating nameplate indicating the
hazardous location temperature code. When combining products within a
system, the most adverse temperature code (lowest "T" number) may be used to
help determine the overall temperature code of the system. Combinations of
equipment in your system are subject to investigation by the local Authority
Having Jurisdiction at the time of installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en
environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux.
Chaque produit est livré avec des marquages sur sa plaque d'identification qui
indiquent le code de température pour les environnements dangereux. Lorsque
plusieurs produits sont combinés dans un système, le code de température le plus
défavorable (code de température le plus faible) peut être utilisé pour déterminer le
code de température global du système. Les combinaisons d'équipements dans le
système sont sujettes à inspection par les autorités locales qualifiées au moment de
l'installation.
WARNING:
Explosion Hazard –
• Do not disconnect equipment unless power has been
removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless
power has been removed or the area is known to be
nonhazardous. Secure any external connections that mate
to this equipment by using screws, sliding latches,
threaded connectors, or other means provided with
this product.
• Substitution of components may impair suitability for Class
I, Division 2.
• If this product contains batteries, they must only be
changed in an area known to be nonhazardous.
AVERTISSEMENT:
Risque d’Explosion –
• Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher les connecteurs. Fixer tous les
connecteurs externes reliés à cet équipement à l'aide de vis,
loquets coulissants, connecteurs filetés ou autres moyens fournis
avec ce produit.
• La substitution de composants peut rendre cet équipement
inadapté à une utilisation en environnement de Classe I, Division 2.
• S'assurer que l'environnement est classé non dangereux avant de
changer les piles.
European Hazardous Location Approval
The following applies to products marked
,
II 3 G:
• Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design
and construction of such equipment given in Annex II to Directive 2014/34/EU. See the EC Declaration of Conformity at
for details.
• The type of protection is Ex nA IIC T4 Gc according to EN 60079-15.
• Comply to standards: EN 60079-0:2012+A11:2013, EN60079-15:2010, reference certificate number DEMKO13ATEX1325026X.
• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and
for short periods. Such locations correspond to Zone 2 classification according to ATEX directive 2014/34/EU.
• May have catalog numbers followed by a "K" to indicate a conformal coating option.