Chapter 6
Safety System Application Guide
Digital Guard I/O Module Faceplate Overview
The faceplate toolbar includes these buttons:
• The
Alarm
button indicates a Guard I/O module fault condition and activates the Error Content view. A black
bell indicates normal status, with no faults. A yellow-black flashing bell indicates a fault condition.
• The
Configuration
button lets you edit the Guard I/O faceplate name or Device Descriptions.
• The
Input/Output Selector
buttons let you select which view is shown.
• The
Help
button let you select Help information for the view.
To close the faceplate, click the Close button in the upper right corner of the display.
Digital Guard I/O Module Faceplate Input Status View – Demand Indication
This Guard I/O faceplate view illustrates a 16-point Guard I/O module’s 0…7 input channel status. The IN 0-7 button is
lighter to confirm this view. The faceplate provides State, Demand, and Cycle indication for each input.
Faceplate Toolbar
Status Indicators
Command Buttons
Close
{
Indicator
Color
Description
Action Required
State
Gray De-energized
(OFF)
None
Orange Energized
(ON)
None
Red
Faulted
Clear the Input/Output (device) fault.
Demand
Gray
No Demand on input
None
Orange
Input in Demand
(1)
(1) A high-to-low transition of the input causes a demand.
Set inputs (devices) to active state, if necessary. Press Demand Reset.