Publication 1734-UM001D-EN-P - April 2008
162
Troubleshoot with the Indicators
1734-AENT EtherNet/IP Adapter
System Power
Field Power
43248aent
Module Status
Network Activity
Network Status
POINTBus Status
Module
Status
Network
Activity
Network
Status
1734-AENT
PointBus
Status
Field
Power
System
Power
0 2
0
Indication
Probable Cause
Recommended Action
Module Status
Off
No power applied to device
Apply power to the device.
Flashing
red/green
LED power cycle test (module self-test) present.
None.
Solid green
Device is operating normally.
None.
Flashing red
•
Recoverable fault has occurred.
•
Firmware (NVS) update present.
•
Address switches changed.
1. Complete firmware update.
2. Verify address switches.
Solid red
•
Unrecoverable fault has occurred.
•
Self-test failure present (checksum failure, or ramtest failure at
power cycle).
•
Firmware fatal error present.
Replace adapter.